Plan Review Notes
Plan Review Notes For Permit 01071514
Permit Number 01071514
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT SPEC SHEET WAS
 SUBMITTED FOR HEAT PUMP.
  
 2)NOTE: PLEASE NOTE THAT PER FS/FAC
 61G15-23.002 ALL PLANS THAT ARE SIGNED.
 DATED AND SEALED BY AN ENGINEER NEED TO
 CONTAIN A TITLE BLOCK.
  
 3)NOTE: PLEASE NOTE THAT HEAT PUMP IS
 NOT SHOWN ON ELECTRICAL WIRING DIAGRAM.
  
 4)NOTE: PLEASE NOTE THAT NO LOAD CALCUL-
 -ATIONS WERE SUBMITTED WITH NEW LOADS
 BEING ADDED. PLEASE INCLUDE SHOW SIZE
 OF EXISTING SERVICE
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372