2001-08-02 00:00:00 | *************** UNSAT ***************** | | | | 1)NOTE: PLEASE NOTE THAT SPEC SHEET WAS | | SUBMITTED FOR HEAT PUMP. | | | | 2)NOTE: PLEASE NOTE THAT PER FS/FAC | | 61G15-23.002 ALL PLANS THAT ARE SIGNED. | | DATED AND SEALED BY AN ENGINEER NEED TO | | CONTAIN A TITLE BLOCK. | | | | 3)NOTE: PLEASE NOTE THAT HEAT PUMP IS | | NOT SHOWN ON ELECTRICAL WIRING DIAGRAM. | | | | 4)NOTE: PLEASE NOTE THAT NO LOAD CALCUL- | | -ATIONS WERE SUBMITTED WITH NEW LOADS | | BEING ADDED. PLEASE INCLUDE SHOW SIZE | | OF EXISTING SERVICE | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|