Plan Review Notes For Permit 01071462 |
Permit Number |
01071462 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-08 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT PANEL SCHEDULES | | AND LOAD CALCULATIONS DO NOT INCLUDE ANY | | ANY NEW LOADS FOR HEAT PUMP, PUMP, LIGHT | | ??? PLEASE ALSO NOTE THAT PAGE 2 SHOWS | | FAULT CURRENT CALCULATIONS? PLEASE | | CLARIFY HOW THESE HAVE ANYTHING TO DO | | WITH PLANS FOR POOL?/ | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | THAT INCLUDE ALL NEW LOADS AND PANEL | | SCHEDULES W/ NEW LOADS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVEIW | | 561-659-8096 EXT 8372 |
|