Plan Review Notes
Plan Review Notes For Permit 01071408
Permit Number 01071408
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PER CONTRACT
 SUBMITTED, CONTRACT SHOWS 400K GAS
 HEATER AND 99K HEAT PUMP? WHICH ONE? OR
 BOTH?
 PLEASE NOTE THAT 1ST PAGE OF PLANS SAY
 99K HEAT PUMP.
 PLEASE NOTE THAT ELECTRICAL DIAGRAM
 DOES NOT SHOW ANY HEAT PUMP?
  
 2)NOTE: PLEASE INCLUDE HEAT PUMP IN
 WIRING DETAIL.
 PLEASE SUBMIT LOAD CALCUALTIONS FOR ALL
 NEW LOADS BEING ADDED AND SHOW SIZE
 OF EXISTING SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372