Plan Review Notes For Permit 01071408 |
Permit Number |
01071408 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-02 00:00:00 | ******************* UNSAT ************* | | | | 1)NOTE: PLEASE NOTE THAT PER CONTRACT | | SUBMITTED, CONTRACT SHOWS 400K GAS | | HEATER AND 99K HEAT PUMP? WHICH ONE? OR | | BOTH? | | PLEASE NOTE THAT 1ST PAGE OF PLANS SAY | | 99K HEAT PUMP. | | PLEASE NOTE THAT ELECTRICAL DIAGRAM | | DOES NOT SHOW ANY HEAT PUMP? | | | | 2)NOTE: PLEASE INCLUDE HEAT PUMP IN | | WIRING DETAIL. | | PLEASE SUBMIT LOAD CALCUALTIONS FOR ALL | | NEW LOADS BEING ADDED AND SHOW SIZE | | OF EXISTING SERVICE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|