2001-08-27 00:00:00 | 1) WET FIRE HYDRANTS ARE TO BE PROVIDED | | WITH CONSTRUCTION. A LETTER SUBMITTED | | BY ERIC COOPER OF SCHAEFER, FAGAN | | INDICATES "FIRE HYDRANTS WILL BE | | PROVIDED PRIOR TO CONSTRUCTION OF THE | | MODELS". PLEASE BE ADVISED THAT WET | | FIRE HYDRANTS ARE REQUIRED WHEN THE | | RESIDENTIAL BUILDINGS ARE UNDER | | CONSTRUCTION NOT JUST THE MODELS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|