2001-08-21 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 NONE SHOWN FOR METER/LOAD CENTER.
  
 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  