Plan Review Notes
Plan Review Notes For Permit 01071271
Permit Number 01071271
Review Stop P
Sequence Number 4
Notes
Date Text
2002-01-14 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT K-PLUMB SANITARY RISER DIAGRAM,
 TRAP FOR CAN WASH TO BE UNDERGROUND, NOT
 ON STACK AS SHOWN
  
 2) RISER DIAGRAM, HORIZONTAL DRY VENT
 NOT APPROVED PER SPC SEC 906.2.1
  
 3) SEPARATE PLUMBING PERMIT REQUIRED
  
 4) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED GAS PERMIT REQUIREMENT SHEET
 FOR INFORMATION REQUIRED FOR GAS PLAN
 REVIEW.
  
 5) PLEASE SUBMIT KITCHEN EQUIPMENT IDENT
 IFICATION SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377