Date |
Text |
2001-09-26 00:00:00 | DENIED |
| REFERENCE: SPC-94 - FACBC-97 - SMC-97 |
| 1) PAGES D-1/A-6 PROVIDE SANITARY RISER |
| DIAGRAM AND WATER RISER DIAGRAM FOR NEW |
| SINKS. |
| 2) PAGES D-1/A-6 PLEASE PROVIDE INFOR- |
| MATION FOR STEAM GENERATOR. WHAT IS THE |
| STEAM FOR? PROVIDE PIPING INFORMATION. |
| 3) PAGES D-1/A-7 RELOCATION OF WATER |
| HEATER. PREVIOUS PLAN REVIEW NOT ADDRES- |
| SED. PLEASE SHOW INFORMATION ON WORKING |
| PLATFORM, LIGHT, WALKWAK TO HEATER (MIN- |
| IMUM 24" WIDE) AND ACCESS SIZE. PER |
| SMC-97 SEC 304.4, SPC-94 SEC 501.7. |
| 4) PAGE A-7 PROVIDE DETAILS ON PAN, PAN |
| DRAIN AND T&P DRAIN LINE FROM W/HEATER. |
| SPC-94 SEC 507.8.1,2,2 AND 4. |
| 5) PAGE A-3 PLEASE PROVIDE ROOF DRAIN |
| CALCULATIONS FOR ROOF DRAIN PER SPC-94 |
| SEC 1108. ALSO PROVIDE SECONDARY ROOF |
| DRAIN CALCULATIONS USING SEC 1109. |
| SHOW RISER DIAGRAMS FOR BOTH WITH ALL |
| PIPE SIZES. |
| 6) PAGE A-6 PREVIOUS COMMENTS #1 AND #2 |
| FROM PLAN REVIEW DATED 8-9-01 WERE NOT |
| ADDRESSED. PLEASE SHOW COMPLIANCE FOR |
| DRESSING ROOMS PER FACBC SEC 4.35 THRU |
| 4.35.5. ALSO SHOW COMPLIANCE FOR SHOWERS |
| PER FACBC SEC 4.21 THRU 4.21.4 AND FIG. |
| 35. |
| 7) PAGE A-6 WATER RISER DIAGRAM. PLEASE |
| LOCATE WATER HAMMER ARRESTORS PER MANU- |
| FACTURES INSTALLATION INSTRUCTIONS AND |
| WH-PDI 201, NOT AT TOP OF DROP AS SHOWN. |
| 8) PAGE A-6 PLEASE PROVIDE CALCULATIONS |
| FOR MINIMUM FIXTURES USING SPC-94 TABLE |
| 407. SHOW DETAILS OF ALL RESTROOMS, GIVE |
| ROOM DIMENTIONS ECT. |
| |
| REVIEW BY KEN STEVENS |
| (561) 659-8096 EXT. 8377 |