Plan Review Notes
Plan Review Notes For Permit 01071271
Permit Number 01071271
Review Stop P
Sequence Number 2
Notes
Date Text
2001-09-26 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SMC-97
 1) PAGES D-1/A-6 PROVIDE SANITARY RISER
 DIAGRAM AND WATER RISER DIAGRAM FOR NEW
 SINKS.
 2) PAGES D-1/A-6 PLEASE PROVIDE INFOR-
 MATION FOR STEAM GENERATOR. WHAT IS THE
 STEAM FOR? PROVIDE PIPING INFORMATION.
 3) PAGES D-1/A-7 RELOCATION OF WATER
 HEATER. PREVIOUS PLAN REVIEW NOT ADDRES-
 SED. PLEASE SHOW INFORMATION ON WORKING
 PLATFORM, LIGHT, WALKWAK TO HEATER (MIN-
 IMUM 24" WIDE) AND ACCESS SIZE. PER
 SMC-97 SEC 304.4, SPC-94 SEC 501.7.
 4) PAGE A-7 PROVIDE DETAILS ON PAN, PAN
 DRAIN AND T&P DRAIN LINE FROM W/HEATER.
 SPC-94 SEC 507.8.1,2,2 AND 4.
 5) PAGE A-3 PLEASE PROVIDE ROOF DRAIN
 CALCULATIONS FOR ROOF DRAIN PER SPC-94
 SEC 1108. ALSO PROVIDE SECONDARY ROOF
 DRAIN CALCULATIONS USING SEC 1109.
 SHOW RISER DIAGRAMS FOR BOTH WITH ALL
 PIPE SIZES.
 6) PAGE A-6 PREVIOUS COMMENTS #1 AND #2
 FROM PLAN REVIEW DATED 8-9-01 WERE NOT
 ADDRESSED. PLEASE SHOW COMPLIANCE FOR
 DRESSING ROOMS PER FACBC SEC 4.35 THRU
 4.35.5. ALSO SHOW COMPLIANCE FOR SHOWERS
 PER FACBC SEC 4.21 THRU 4.21.4 AND FIG.
 35.
 7) PAGE A-6 WATER RISER DIAGRAM. PLEASE
 LOCATE WATER HAMMER ARRESTORS PER MANU-
 FACTURES INSTALLATION INSTRUCTIONS AND
 WH-PDI 201, NOT AT TOP OF DROP AS SHOWN.
 8) PAGE A-6 PLEASE PROVIDE CALCULATIONS
 FOR MINIMUM FIXTURES USING SPC-94 TABLE
 407. SHOW DETAILS OF ALL RESTROOMS, GIVE
 ROOM DIMENTIONS ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377