Plan Review Notes For Permit 01071271 |
Permit Number |
01071271 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-09 00:00:00 | DENIED; | | | | 1.PAGE A-6 DRESSING ROOMS SHALL COMPLY | | WITH FACBC SEC. 4.35 THRU 4.35.5. | | 2.SHOWER STALLS SHALL COMPLY WITH FACBC | | SEC. 4.21 THRU 4.21.4, ALSO SEE FIG. | | 35. | | 3.PAGE A-6 WHAT IS 2" PLUMBING DRAIN FOR | | SHOWER DRAIN IS 3" WHAT ELSE IS BEING | | ADDED? | | 4.WATER HEATER MUST BE READILY ACCESS- | | IBLE. IF RELOCATED IN ATTIC A FIXED | | LADDERSHALL BE AVAILABLE AND A WORKING | | PLATFORM MUST BE IN PLACE WITH A LIGHT | | SPC SEC. 501.7. | | 5.WATER HEATER PAN AND DRAIN SHALL | | COMPLY WITH SEC. 507.8.1,2,3, AND .4. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|