Plan Review Notes
Plan Review Notes For Permit 01071271
Permit Number 01071271
Review Stop M
Sequence Number 1
Notes
Date Text
2001-08-14 00:00:00PROVIDE INFORMATION ON CONDENSATE DRAIN
 LOCATION AND TERMINATION.(NOT ON ROOF)
  
 NO ENERGY EFFICIENCY VALUES SHOWN FOR
 AIR HANDLING EQUIPMENT. PROVIDE
 INFORMATION SHOWING COMPLIANCE WITH FL
 ENERGY CODE.
  
 PROVIDE CURB ATTACHMENT INFORMATION
 SHOWING COMPLIANCE WITH WIND LOAD
 (STRUCTURAL SHOWS RAILS NOT CURBS)
  
 EXHAUST PER ASHRAE 62-89 AND SMC
 503.3.2SHALL BE PROVIDED. PROVIDE
 INFORMATION ON FANS AND INSTALLATION
 DETAILS FOR SHOWER AREAS.
  
 CEILING PADDLE FANS TO BE MINIMUM 8 FOOT
 ABOVE FINISHED FLOOR PER SMC 404.3.2
  
 PROVIDE INFORMATION ON EQUIPMENT ACCESS
 ON ROOF. ELECTRIC FOR ROOF EQUIPMENT
 SHALL INCLUDE 115V GFIC OUTLET.
2001-08-13 00:00:00********************DENIED**************
  
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER
 1997 SMC 406.1 AND NFPA 90A 4-4.4.3.