2001-08-14 00:00:00 | PROVIDE INFORMATION ON CONDENSATE DRAIN |
| LOCATION AND TERMINATION.(NOT ON ROOF) |
| |
| NO ENERGY EFFICIENCY VALUES SHOWN FOR |
| AIR HANDLING EQUIPMENT. PROVIDE |
| INFORMATION SHOWING COMPLIANCE WITH FL |
| ENERGY CODE. |
| |
| PROVIDE CURB ATTACHMENT INFORMATION |
| SHOWING COMPLIANCE WITH WIND LOAD |
| (STRUCTURAL SHOWS RAILS NOT CURBS) |
| |
| EXHAUST PER ASHRAE 62-89 AND SMC |
| 503.3.2SHALL BE PROVIDED. PROVIDE |
| INFORMATION ON FANS AND INSTALLATION |
| DETAILS FOR SHOWER AREAS. |
| |
| CEILING PADDLE FANS TO BE MINIMUM 8 FOOT |
| ABOVE FINISHED FLOOR PER SMC 404.3.2 |
| |
| PROVIDE INFORMATION ON EQUIPMENT ACCESS |
| ON ROOF. ELECTRIC FOR ROOF EQUIPMENT |
| SHALL INCLUDE 115V GFIC OUTLET. |
2001-08-13 00:00:00 | ********************DENIED************** |
| |
| |
| |
| PLEASE PROVIDE THE FOLLOWING INFORMATION |
| FOR REVIEW. |
| |
| |
| 1.OUTSIDE AIR CALCULATIONS AS PER |
| ASHRAE 62-89. |
| |
| 2.AIR BALANCE SCHEDULE TO SHOW |
| COMPLIANCE WITH 1997 SMC 501.2. |
| |
| 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| WITH NOTIFICATION TO ALARM/STROBE IN |
| NORMALLY OCCUPIED AREAS AS PER |
| 1997 SMC 406.1 AND NFPA 90A 4-4.4.3. |