Plan Review Notes For Permit 01071271 |
Permit Number |
01071271 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-13 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT ALL BRANCH | | CIRCUIT #`S NEED TO BE SHOWN PLANS AND | | CORRELATE WITH SUBMITTED PANEL SCHEDULES | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | FOR ADDING LOADS TO EXISTING.215-5 | | | | 3)NOTE: PLEASE CLARIFY EQUIPMNET GROUND- | | -ING METHOD. SIZE PER 250-122 | | | | 4)NOTE: PLEASE CLARIFY BONDING OF NEW | | FOOTER STEEL OF NEW ADDITION. 250-50 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|