Plan Review Notes
Plan Review Notes For Permit 01071271
Permit Number 01071271
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-13 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S NEED TO BE SHOWN PLANS AND
 CORRELATE WITH SUBMITTED PANEL SCHEDULES
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ADDING LOADS TO EXISTING.215-5
  
 3)NOTE: PLEASE CLARIFY EQUIPMNET GROUND-
 -ING METHOD. SIZE PER 250-122
  
 4)NOTE: PLEASE CLARIFY BONDING OF NEW
 FOOTER STEEL OF NEW ADDITION. 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372