Plan Review Notes
Plan Review Notes For Permit 01070890
Permit Number 01070890
Review Stop E
Sequence Number 2
Notes
Date Text
2001-11-06 00:00:00***************UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW
 SHOWING A NEW 200AMP MAIN AND PANEL
 AND CONDUCTORS STILL REFLECT OLD 150A
 SERVICE. PLEASE CORRELATE WIRE SIZE WITH
 OCP.310-15.
  
 2)NOTE:PLEASE NOTE THAT EACH HANDWRITTEN
 CHANGEON PLANS MUST BE EITHER SIGNED,
 DATED OR RE-PRINT AND SIGN, AND SEAL.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372