2001-11-13 00:00:00 | ************** UNSAT ******************* | | | | 1)NOTE: PLEASE NOTE THAT THE SERVICE | | HAS NOW BEEN INCREASED TO 200A AND THE | | CONDUCTORS ARE STILL SHOWN AT #1 (150A) | | PLEASE CORRECT. | | | | 2)NOTE: PLEASE CLARFIY MEANS OF EGRESS | | LIGHTING COMING FROM NEW TEMP OFFICES | | TO OUTSIDE. 210-70. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|