Plan Review Notes For Permit 01070805 |
Permit Number |
01070805 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-31 00:00:00 | CHECKLIST: | | 1-OPEN STRUCTURE NEEDS TO BE DESIGNED | | USING SECTION 308 OF SSTD 10-97, WHICH | | IS THE PRESCRIPTIVE STANDARD ADOPTED | | WHEN THE DESIGNER IS NOT A REGISTERED | | ARCHITECT OR ENGINEER. SEC. 104.2.3 OF | | CITY AMENDMENTS TO SBC 1997. | | 2-CLARIFY IF EXISTING WINDOWS ARE GOING | | TO BE ENCLOSED OR NOT. SEE NOTES ON | | PLAN VIEW & ELECTRICAL LAYOUT. IF SO, | | WHAT'S GOING TO HAPPEN TO THE EXISTING | | BATH VENTILATION AND EXISTING BEDROOM | | EMERGENCY EGRESS. | | 3-SPECIFY VENTILATION FOR FLAT ROOF AS | | REQUIRED BY SEC. 2309.7.2 SBC 1997. | | 4-SEE PLANS FOR ADDITIONAL COMMENTS. | | PLEASE RETURN REVIEWED SET AFTER | | CORRECTIONS ARE DONE TO THE ORIGINAL | | DRAWINGS IN ORDER TO EXPEDITE THE | | REVIEW PROCESS. | | 5-OWES $188.55 FOR LOW VALUATION | | DECLARED ON APPLICATION AND RADON FEES | | 6-PROVIDE PRODUCT APPROVAL FOR: | | -FLAT ROOF SYSTEM. | | -DOORS AND WINDOWS IF THEY ARE GOING | | TO BE REMOVED. |
|