Plan Review Notes For Permit 01070803 |
Permit Number |
01070803 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-18 00:00:00 | ********************DENIED************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW. | | | | | | 1.AS INDICATED ON PLAN SHEET #1, | | 3M FIRE MASTER WRAP IS BEING | | INSTALLED.PLEASE SUBMIT 2 COPIES | | OF MANUFACTURER SUBMITTAL DATA AND | | INSTALLATION DETAILS. | | | | 2.MANUFACTURER SUBMITTAL DATA/DETAIL | | ON HOOD. | | | | 3.AS NOTED ON PLAN SHEET #2, 1/4" PER | | FOOT PITCH ON GREASE DUCT...THIS | | SHALL BE A MINIMUM OF 1" PER FOOT | | AS REQUIRED BY THE 1997 SMC 505.4. | | | | 4.MINIMUM OF 10' BETWEEN EXHAUST | | AND AIR INTAKES, 1997 SMC 506.1. | | | | NOTE:ADDITIONAL PERMIT REQUIRED FOR | | FIRE SUPRESSION SYSTEM.PLEASE | | SUBMIT PLANS WITH PERMIT | | APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|