2002-04-10 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) THE MINIMUM FOOTING THICKNESS OF A |
| MONOLITHIC SLAB ON GRADE IS 20 INCHES |
| PER SSTD 10-97 SECT. 303.3.1. PLEASE |
| CORRECT. |
| |
| 2) THE MINIMUM ANCHOR BOLT DIAMETER IS |
| 5/8" WITH A MINIMUM OF 7" EMBEDMENT. THE |
| WASHERS ARE REQUIRED TO BE 3"X 3"X 1/8" |
| PER SSTD 10-97 SECT. 303.3.2. PLEASE |
| CORRECT. |
| |
| 3) A DOUBLE LAYER OF 6X6 NO.10 WELDED |
| WIRE FABRIC 3 FEET WIDE SHALL BE |
| PROVIDED AROUND THE PERIMETER OF THE |
| SLAB PER SSTD 10-97 SECT. 304.1.3. |
| |
| 4) INDICATE THE LOCATION OF HOLDDOWN |
| CONNECTORS REQUIRED AT THE EXTERIOR |
| SHEAR WALLS PER SSTD 10-97 SECT.305.4. |
| |
| 5) A MECHANICAL EXHAUST VENT TO THE |
| EXTERIOR IS REQUIRED IN THE EXISTING |
| BATHROOM IN WHICH THE WINDOW IS BEING |
| REMOVED. |
| |
| 6) THE WEST ELEVATION OF THE ADDITION |
| DOES NOT COMPLY WITH TABLE 600 OF THE |
| 97 SBC FOR THE PERCENTAGE OF WALL AREA |
| OPENINGS ALLOWED BASED ON THE INFO THAT |
| WAS SUBMITTED. THE WALL AREA OF THE |
| EXISTING STRUCTURE CAN BE USED IF THE |
| OPENINGS (WINDOW, DOOR, ETC.) ARE |
| INDICATED ON THE PLANS. TWENTY PERCENT |
| OF THE WALL AREA (FLOOR TO CEILING HT.) |
| IS ALLOWED AS OPENINGS BASED ON A |
| DISTANCE OF 3'TO 10'TO THE PROPERTY |
| LINE. |
| |
| 7) THE SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN IS REQUIRED |
| ON THE DRAWINGS PER CITY OF W.P.B. |
| AMENDMENTS TO THE 97 SBC SECT. 104.2.1. |
| |
| 8) THE NOTES FOR ROOF SHEATHING NAILING |
| REQUIREMENTS ARE NOT CLEAR. IN ZONES 1& |
| 2 THE REQUIRED NAIL SPACING IS 6" O.C. |
| ON THE EDGES AND 6"O.C. INTERMEDIATE. IN |
| ZONE 3 THE NAIL SPACING IS 4"O.C. AT THE |
| EDGES AND 6"O.C. INTERMEDIATE. SEE CITY |
| OF WPB AMENDMENTS TO 97 SBC SECT. 2306. |
| PLEASE CLARIFY. |
| |
| 9)THE TOTAL NOMINAL THICKNESS FOR STUCCO |
| ON METAL LATH OVER SOLID BASE IS 7/8" |
| PER 97SBC SECT.2405.2.1 AND ASTM C 926. |
| PLEASE CORRECT. |
| |
| 10) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL WINDOW MULLIONS THAT WILL |
| BE USED TO CONNECT WINDOWS IN ADDITION. |
| |