2002-04-04 00:00:00 | ***************** UNSAT **************** |
| |
| 1)NOTE: PLEASE NOTE THAT NOTES FROM |
| FIRST AND SECOND REVIEW ARE STILL NOT |
| ADDRESSED???? |
| |
| 2)NOTE: PLEASE NOTE MISSING REQ`D BATH |
| RECEPT PER 210-52D, ALSO ALL TO BE |
| SHOWN AS GFI/GFI PROTECTED.210-8 |
| |
| 3)NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 4)NOTE: PLEASE NOTE THAT PANEL SCHEDULE |
| AND LOAD CALCULATIONS,,,DO NOT CORRELATE |
| PLEASE NOTE THAT THERE ARE MANY THINGS |
| THAT DO NOT MATCH UP??? |
| |
| 5)NOTE: PLEASE NOTE THAT PLANS ARE NOTED |
| THAT NO CENTRAL A/C IS EXISTING AND YET |
| THEY ARE SHOWN ON LOAD CALCULATIONS????? |
| PLEASE CLARIFY!!! IF NEW SHOW EQUIPMNET |
| AND DISC`S PER 440-11. |
| IF THERE IS NONE THEN PLEASE REMOVE. |
| |
| 6)NOTE: PANEL IS SHOWN TO BE 125A AS |
| EXISTING AND ALSO SHOWN AS 150A AS EXIST |
| ING??? WHICH ONE. ALSO SHOWN AS 15A |
| ABOVE LOAD CALCS. |
| |
| 7)NOTE: PLEASE NOTE THAT BOTH SMALL |
| APPLIANCE CIRCUITS ARE SHOWN AS 2000W`S |
| PLEASE SEE 210-52B, 210-11C-1. |
| |
| 8)NOTE: PLEASE NOTE THAT THERE IS |
| NOTHING SHOWN FOR "HOW" DETACHED GARAGE |
| IS FED??? MEANS OF DISC? 225-31, |
| GROUNDING??250-32 |
| |
| 9)NOTE: PLEASE HAVE PLANS PLACED INTO |
| TWO SET FOR REVIEW. PLEASE KEEP ALL OLD |
| SETS SEPARATE. PLEASE DATE PLANS AS REQ` |
| D. |
| PLEASE CLARIFY PROVIDE INFORMATION ON |
| PERSON WHO DREW PLANS. ARCH/OR DRAFTSMAN |
| PLEASE NOTE THAT IF DONE BY AN ARCH, |
| THEN PLANS MUST BE SIGNED AND SEALED BY |
| THAT PERSON. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. PLEASE NOTE ONCE AGAIN, IF THERE |
| ARE ANY QUESTIONS,,,,,,, PLEASE CALL!!!! |
| IF A MEETING IS NEEDED TO GO OVER PLANS |
| AND CODE ISSUES,,,,, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |