Plan Review Notes
Plan Review Notes For Permit 01070708
Permit Number 01070708
Review Stop E
Sequence Number 3
Notes
Date Text
2002-04-04 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOTES FROM
 FIRST AND SECOND REVIEW ARE STILL NOT
 ADDRESSED????
  
 2)NOTE: PLEASE NOTE MISSING REQ`D BATH
 RECEPT PER 210-52D, ALSO ALL TO BE
 SHOWN AS GFI/GFI PROTECTED.210-8
  
 3)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 AND LOAD CALCULATIONS,,,DO NOT CORRELATE
 PLEASE NOTE THAT THERE ARE MANY THINGS
 THAT DO NOT MATCH UP???
  
 5)NOTE: PLEASE NOTE THAT PLANS ARE NOTED
 THAT NO CENTRAL A/C IS EXISTING AND YET
 THEY ARE SHOWN ON LOAD CALCULATIONS?????
 PLEASE CLARIFY!!! IF NEW SHOW EQUIPMNET
 AND DISC`S PER 440-11.
 IF THERE IS NONE THEN PLEASE REMOVE.
  
 6)NOTE: PANEL IS SHOWN TO BE 125A AS
 EXISTING AND ALSO SHOWN AS 150A AS EXIST
 ING??? WHICH ONE. ALSO SHOWN AS 15A
 ABOVE LOAD CALCS.
  
 7)NOTE: PLEASE NOTE THAT BOTH SMALL
 APPLIANCE CIRCUITS ARE SHOWN AS 2000W`S
 PLEASE SEE 210-52B, 210-11C-1.
  
 8)NOTE: PLEASE NOTE THAT THERE IS
 NOTHING SHOWN FOR "HOW" DETACHED GARAGE
 IS FED??? MEANS OF DISC? 225-31,
 GROUNDING??250-32
  
 9)NOTE: PLEASE HAVE PLANS PLACED INTO
 TWO SET FOR REVIEW. PLEASE KEEP ALL OLD
 SETS SEPARATE. PLEASE DATE PLANS AS REQ`
 D.
 PLEASE CLARIFY PROVIDE INFORMATION ON
 PERSON WHO DREW PLANS. ARCH/OR DRAFTSMAN
 PLEASE NOTE THAT IF DONE BY AN ARCH,
 THEN PLANS MUST BE SIGNED AND SEALED BY
 THAT PERSON.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE ONCE AGAIN, IF THERE
 ARE ANY QUESTIONS,,,,,,, PLEASE CALL!!!!
 IF A MEETING IS NEEDED TO GO OVER PLANS
 AND CODE ISSUES,,,,, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372