Date |
Text |
2002-01-03 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) INDICATE ON PLANS THE METHOD OF |
| OF ATTACHMENT THAT WILL BE USED TO |
| CONNECT THE WOOD FRAME WALLS OF THE |
| ADDITION TO THE EXISTING STRUCTURE. |
| |
| 4) PLEASE CLARIFY IF THE PLANS ARE TO BE |
| CERTIFIED BY THE ENGINEER (JOHN HOLT) AS |
| INDICATED BY THE DESIGN CERTIFICATION |
| FORM THAT YOU SUBMITTED (NEEDS EMBOSSED |
| SEAL) OR IS BEING DESIGNED TO COMPLY |
| WITH SSTD 10-97, WHICH DOES NOT REQUIRE |
| AN ARCHITECT OR ENGINEER. |
| |
| 5) PROVIDE ENERGY CALCULATIONS FOR THE |
| NEW ADDITION AS REQUIRED BY THE 1997 |
| FLORIDA ENERGY EFFICIENCY CODE SEC. |
| 101.2.2 AND 101.5.3. |
| |
| 6) NOTES FOR GARAGE INDICATE 4:12 ROOF |
| PITCH AND DRAWINGS INDICATE 3:12 PITCH. |
| PLEASE CORRECT. |
| |
| 7) ROOF SHEATHING IS REQUIRED TO BE |
| NAILED 4" O.C. AT EDGES AND 6" O.C. |
| INTERMEDIATE WITHIN 5' OF ROOF EDGE |
| INCLUDING 1' OVERHANG AT GABLE ENDS |
| (ZONE 3). CITY OF WPB AMENDMENTS TO |
| 97 SBC SEC. 2306. |
| |
| 8) INDICATE ATTIC ACCESS FOR ADDITION |
| AND GARAGE. 97 SBC 2309.6 |
| |
| 9) INDICATE THE TYPE AND SIZE OF THE TWO |
| WINDOWS IN THE FLORIDA ROOM. |
| |
| 10) PROVIDE ADDITIONAL COPIES OF ALL |
| PRODUCT APPROVALS THAT WERE SUBMITTED. |
| TWO COPIES ARE REQUIRED. |
| |
| 11)PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. REQUIRED |
| FOR ALL EXTERIOR GLAZED OPENINGS ON |
| NEW ADDITION AND GARAGE. |
| |
| 12) PROVIDE TWO LEGIBLE COPIES OF SURVEY |
| INDICATING THE FRONT, REAR AND SIDE |
| SET BACKS TO THE ADDITION AND THE |
| DETACHED GARAGE. |
| |
| 13) THE BOTTOM OF THE FOOTING SHALL BE |
| A MINIMUM OF 12" BELOW FINISH GRADE, AND |
| AN APPROVED STUCCO STOP PLACED NOT LESS |
| THAN 6" ABOVE FINISH GRADE IS REQUIRED |
| TO TERMINATE THE STUCCO AT THE BASE OF |
| THE WALL. PLEASE INDICATE THESE ITEMS ON |
| THE PLANS. |
| |
| IF YOU HAVE QUESTIONS PLEASE CALL: |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |