Plan Review Notes
Plan Review Notes For Permit 01070708
Permit Number 01070708
Review Stop R
Sequence Number 1
Notes
Date Text
2001-07-31 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE ENGINEER'S TITLE BLOCK IS
 REQUIRED ON EACH SHEET OF THE PLANS
 THATARE SIGNED AND SEALED BY HIM.
  
 3) THE BUCK DETAILS AND WALL DETAIL ARE
 ILLEGIBLE. PLEASE PROVIDE PLANS THAT
 ARECLEAR AND READABLE.
  
 4) INDICATE METHODS OF ATTACHMENT FOR
 SECURING FRAME WALLS AND CONCRETE FOOT-
 INGS TO EXISTING STRUCTURE.
  
 5) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL
 J)AS REQUIRED BY THE 1997 FLORIDA
 ENERGYEFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 6) INDICATE SPECIAL ROOF SHEATHING
 NAILING ZONES COMPLYING WITH SECTION
 2306 OF THE CITY AMENDMENTS TO THE 97
 SBC.
  
 7) PROVIDE GABLE END BRACING DETAILS.
  
 8) INDICATE HOW ATTIC ACCESS TO NEW
 ADDITION WILL BE ACHIEVED.
  
 9) THE ROOF PLANS INDICATE # 11
 CONNECTORS FROM THE SCHEDULE FOR
 ATTACHING THE TRUSSES TO THE WALLS.
 THESE CONNECTORS ARE FOR WOOD TRUSS TO
 CONCRETE BEAM CONNECTIONS. PLEASE
 INDICATE THE APPROPRIATE CONNECTORS
 WHICH ARE CAPABLE OF WITHSTANDING THE
 CALCULATED LOADS.
  
 10) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR ALL EXTERIOR WINDOW AND
 DOOR OPENINGS OF ADDITION AND DETACHED
 GARAGE.
  
 11) INDICATE THE SPECIFICATE TYPES OF
 CONNECTORS THAT WILL BE USED TO PROVIDE
 A CONTINOUS TIE FROM THE FOUNDATION TO
 THE ROOF.
  
 12) INDICATE THE TYPES AND SIZES OF THE
 WINDOWS AND DOORS ON THE PLANS.
  
 13) TABLE 600 IN THE 97 SBC IS USED TO
 DETERMINE THE PERCENTAGE OF WALL AREA
 THAT IS ALLOWED AS OPENINGS BASED ON
 THEDISTANCE TO THE PROPERTY LINE OR
 ASSUMEDPROPERTY LINE. PLEASE PROVIDE
 BOTH SIDE AND REAR ELEVATIONS FOR THE
 ADDITION ANDALL FOUR ELEVATIONS FOR THE
 GARAGE.
  
 14) PROVIDE TWO (2) LEGIBLE COPIES OF
 THE SURVEY, WHICH INDICATE THE
 DISTANCESTO THE PROPERTY LINES AND THE
 DISTANCE
 BETWEEN THE ADDITION AND THE GARAGE.
  
 15) THE BEDROOM WINDOW MUST COMPLY WITH
 EGRESS REQUIREMENTS. 97 SBC SEC. 1005.4
  
 16) SAFETY GLASS IS REQUIRED IN THE
 BATHROOM WINDOWS IF LOCATED LESS THAN
 60"
 ABOVE THE TUB DRAIN INLET.
  
 17) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIAL
 - GARAGE DOOR
 - WINDOWS (THE ONE SUBMITTED IS
 EXPIRED)- SIDE SWING DOOR (THE ONE
 SUBMITTED
 DOES NOT CORRESPOND TO THE PLANS)
 NOTE: TWO COPIES ARE REQUIRED
  
 18) THE BOTTOM OF THE FOOTINGS SHALL BE
 A MINIMUM OF 12" BELOW FINISH GRADE.
 97 SBC SEC.1804.1.3
  
 19) WHERE LATH AND STUCCO IS APPLIED
 OVER THE EXTERIOR OF WOOD FRAME
 CONSTRUCTION, AN APPROVED WEEP SCREED
 (STUCCO STOP) PLACED NOT LESS THAN 6"
 ABOVE FINISH GRADE SHALL BE USED TO
 TERMINATE STUCCO AT THE BASE OF THE
 WALL2304.2.5 OF CITY AMENDEMENTS TO 97
 SBC.
  
 20) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF
 ANCHORS TO BE USED FOR STORM PANELS.
 NOTE: MISSLE IMPACT PROTECTION IS
 REQUIRED FOR ALL GLAZED EXTERIOR
 OPENINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW