2001-08-02 00:00:00 | **************** UNSAT ***************** |
| |
| 1)NOTE: PLEASE NOTE THAT RECEPTS IN GAR |
| ARE TO BE GFI/GFI PROTECTED PER 210-8. |
| |
| 2)NOTE: PLEASE SUBMIT INFORMATION FOR |
| MEANS OF DISCONNECT AT DETACHED |
| STRUCTURE.225-31 |
| |
| 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| |
| 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| PLEASE SUBMIT A PANEL SCHEDULE FOR |
| REQ`DCIRCUITS (EXISTING AND NEW) |
| |
| 5)NOTE: PLEASE CLARIFY NEW A/C SHOWN ON |
| RISER DIAGRAM? PLEASE SHOW ON PLANS AND |
| PROVIDE A/C RECEPT AND DISC`S PER |
| 440-11AND 309.1 (MECH CODE) |
| |
| 6) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 7) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| BY 210-52E OF THE NEC. |
| MISSING REAR. |
| |
| PLEASE MAKE NOTE THAT IF THERE IS GOING |
| TO BE ANY CATV AND/OR TELEPHONE IN NEW |
| ADDITION, THEN IT NEEDS TO BE DRAWN ON |
| PLANS. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |