Plan Review Notes
Plan Review Notes For Permit 01070708
Permit Number 01070708
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT RECEPTS IN GAR
 ARE TO BE GFI/GFI PROTECTED PER 210-8.
  
 2)NOTE: PLEASE SUBMIT INFORMATION FOR
 MEANS OF DISCONNECT AT DETACHED
 STRUCTURE.225-31
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 PLEASE SUBMIT A PANEL SCHEDULE FOR
 REQ`DCIRCUITS (EXISTING AND NEW)
  
 5)NOTE: PLEASE CLARIFY NEW A/C SHOWN ON
 RISER DIAGRAM? PLEASE SHOW ON PLANS AND
 PROVIDE A/C RECEPT AND DISC`S PER
 440-11AND 309.1 (MECH CODE)
  
 6) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 MISSING REAR.
  
 PLEASE MAKE NOTE THAT IF THERE IS GOING
 TO BE ANY CATV AND/OR TELEPHONE IN NEW
 ADDITION, THEN IT NEEDS TO BE DRAWN ON
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372