Plan Review Notes
Plan Review Notes For Permit 01070586
Permit Number 01070586
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:001) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 2) NO FIRE ALARM SYSTEM DEVICES SHOWN
 ON PLANS. ARE THERE ANY EXISTING OR
 NEW FIRE ALARM DEVICES PLANNED FOR THE
 SPACE.
 3) SELF-CLOSING DEVICES REQUIRED FOR
 ALL RATED FIRE DOORS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910