Plan Review Notes For Permit 01070579 |
Permit Number |
01070579 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-02 00:00:00 | DENIED; | | 1.HANDICAP TOILET MEASUREMENT OFF FINISH | | WALL SHALL BE 18". FACBC FIG.28. | | 2.DRINKING FOUNTAIN TO COMPLY WITH 4.1.3 | | AND 4.15. | | 3.MEN'S ROOM SHOULD HAVE A FLOOR DRAIN | | ALSO. | | 4.FLOOR DRAINS SHALL HAVE TRAP PRIMERS | | SPC SEC 409.4.1.1. | | 5.DRINKING FOUNTAIN MAXIMUM HIGHTH TO | | ORIFICE IS 36" FACBC FIG. 27(A). | | 6.NOTE 8, ALL WATER HAMMER ARRESTERS TO | | BE ENGINEERED PER SPC SEC. 607.8.2 | | AND 607.8.3. LOCATE PER MANUFACTOR | | RECOMMENDATIONS. | | 7.NOTE 10, BOTTLED WATER COOLER IS NOT | | A PLUMBING FIXTURE AND CAN NOT BE USED | | AS AN ALTERNATE METHOD. SEE TABLE 407 | | UNDER MISCELLANEOUS FIXTURES. ALSO SEE | | CHAPTER 2 DEFINITIONS "PLUMBING | | FIXTURES. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|