Plan Review Notes For Permit 01070579 |
Permit Number |
01070579 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-25 00:00:00 | 1) PLANS NEED TO CLEARLY IDENTIFY FIRE | | RATED WINDOWS LOCATED WITHIN 10 FEET OF | | THE NEW METAL FIRE STAIRS LOCATED ON | | THE NORTH SIDE OF THE BUILDING. IT IS | | KNOWN THAT THE STAIRS HAVE BEEN | | INSTALLED BUT IT IS NOT KNOWN IF THE | | RATED WINDOWS HAVE ALSO BEEN INSTALLED. | | 2) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | 3) PLEASE PROVIDE DETAILS ON EXISTING | | ELEVATOR. IS THE ELEVATOR EQUIPPED | | WITH PHASE ONE AND PHASE TWO ELEVATOR | | RECALL AND WHAT IS THE TRAVEL DISTANCE | | FOR IT. | | 4) PLEASE PROVIDE MORE DETAILS ON STEPS. | | WHAT DIRECTION DO YOU GO. UP OR DOWN. | | IF YOU TRAVEL UPWARD, DO YOU STAND ON | | A STEP AND OPEN THE DOOR OR IS THERE A | | LANDING. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|