Plan Review Notes For Permit 01070579 |
Permit Number |
01070579 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-07 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT | | #`S NEED TO BE SHOWN ON PLANS. PLEASE | | NOTE THAT OUTLET CIRCUITS ARE SHOWN BUT | | NOT FOR LIGHTING SHOWN. | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | PLEASE NOTE THAT AIC RATING IS SHOWN FOR | | PANEL BUT NEEDED FOR MAIN DISCONNECT. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|