2001-08-07 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT
 #`S NEED TO BE SHOWN ON PLANS. PLEASE
 NOTE THAT OUTLET CIRCUITS ARE SHOWN BUT
 NOT FOR LIGHTING SHOWN.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING IS SHOWN FOR
 PANEL BUT NEEDED FOR MAIN DISCONNECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372