Plan Review Notes
Plan Review Notes For Permit 01070299
Permit Number 01070299
Review Stop P
Sequence Number 3
Notes
Date Text
2002-01-08 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 PREVIOUS COMMENTS FROM 7-27-01
 4) SHT P-2 CONDENSATE DRAIN TIED INTO
 STORM DRAIN SHALL HAVE A RELIEF VENT IN
 CASE OF BACK-UP OF STORM WATER.
 8) SHT A1.3, TURNING RADIUS TO BE IN
 TOILET ROOM NOT STALL. CLEAR FLOOR SPACE
 TO BE SHOWN FOR HDCP URNAL AND DOOR FROM
 STALL SHALL NOT SWING INTO THAT CLEAR
 FLOOR SPACE.
 PREVIOUS COMMENTS FROM 11-18-01
 1) SHT A1.4 TEACHERS PLANNING ROOM, SHOW
 CLEAR FLOOR SPACE FOR SINK AND KNEE
 CLEARANCE PER FACBC SEC 4.24
 2) SHT A1.3, RM #102 PROVIDE CODE REFER-
 ENCE, CHILDERNS H/C PLUMBING FIXTURES
 FOR DIMENSIONS, GRAB BARS, DOOR SWING.
 NOT FOUND, PLEASE CALL OUT RESPONSE.
 4) SHT P-2 RM'S 401 & 501, BACKFLOW DE-
 VISES SHALL BE NO HIGHER THAN 4' ABOVE
 FINISH FLOOR FOR SERVICE.
 5) SHT P-3 WASTE & VENT RISER, TAB 714.1
 FIXTURE LOAD NOT ADDRESSED, REQUIRED TO
 SIZE BLDG DRAIN.
 5B) SHT P-3 TWO WAY C/O AT BLDG DRAIN &
 BLDG SEWER NOT ADDRESSED. SPC SEC 710(6)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377