Plan Review Notes
Plan Review Notes For Permit 01070299
Permit Number 01070299
Review Stop P
Sequence Number 2
Notes
Date Text
2001-11-18 00:00:00PLUMBING PLAN REVIEW,DENIED
 CODE REFERENCES STANDARD PLUMBING-94
 FLORIDA ACCESSIBILITY CODE-97
 PREVIOUS COMMENTS NOT ADDRESSED 07-27-01
 (4) SHT P-2 CONDENSATE DRAIN TERMINATION
 NOT SHOWN ON SHT C-1, CIVIL PLANS.
 (8) SHT A1.3, 1ST, 2ND FLR BOYS & GIRLS
 TOILET RM'S, COMPLY W/SEC 4.2.3 & 4.22.3
 TOILET RM WHEEL CHAIR TURNING SPACE, SEE
 FIG 30(E) FOR STALLS, URINALS MAX HIGTH
 SEC 4.18.2, CLEAR FLR SPACE SEC 4.18.3
 NEW COMMENTS DATED 11-18-01PES
 (1) SHT A1.4 TEACHERS PLANNING RM OR
 ( BREAK RM.) SEC 4.24 SINK HGTH, 34"FF
 CLEAR FLR SPACE 30"X 48", KNEE CLEARANCE
 (2) SHT A1.3, RM #102 PROVIDE CODE REFER
 ENCE, CHILDERNS H/C PLUMBING FIXTURES.
 FOR DIMENSIONS, GRAB BARS, DOOR SWING.
 (3) SHT A2.1,2 PARAPET DETAIL, PROVIDE
 CALCULATIONS FOR SCUPPER DRAINS, SIZE
 LOCATION, 1/2 THE VERTICAL WALLS 1108.3
 SEE TAB 1109.3, RATE OF RAINFALL 8.5"
 (4) SHT P-2 RM 401,501 JANITORS CLOSET
 SPRINKLER HEAD, COMPLY WITH SEC 606.3 &
 606.1 ADEQUATE PROTECTION OF POTABLE
 WATER SHALL BE PROVIDED FROM UNSAFE
 SYSTEM TO A SAFE SYSTEM, PROVIDE INFOR-
 MATION ON TYPE OF BACKFLOW PROTECTION.
 (5A)SHT P-3 WASTE & VENT RISER,TAB 714.1
 PROVIDE FIX UNIT LOAD TO SIZE BLDG DRAIN
 (5B) TWO WAY CO. REQUIRED AT JUNCTION OF
 BUILDING DRAIN AND THE BUILDING SEWER.
 SEC 710(6).
 (6) SHT P-3,4 DETAILS OF WATER PIPING,
 COMPLY W.SEC 607.8.1,WATER HAMMER ARREST
 ORS SHALL BE SIZED AND INSTALLED AS PER
 PDI-WH201, NOT AT THE HIGH POINT OF THE
 SYSTEM.SPECIFY TYPE AND MANFACTURE.
 END OF COMMENTSPAUL SCHMITZ