2001-11-18 00:00:00 | PLUMBING PLAN REVIEW,DENIED |
| CODE REFERENCES STANDARD PLUMBING-94 |
| FLORIDA ACCESSIBILITY CODE-97 |
| PREVIOUS COMMENTS NOT ADDRESSED 07-27-01 |
| (4) SHT P-2 CONDENSATE DRAIN TERMINATION |
| NOT SHOWN ON SHT C-1, CIVIL PLANS. |
| (8) SHT A1.3, 1ST, 2ND FLR BOYS & GIRLS |
| TOILET RM'S, COMPLY W/SEC 4.2.3 & 4.22.3 |
| TOILET RM WHEEL CHAIR TURNING SPACE, SEE |
| FIG 30(E) FOR STALLS, URINALS MAX HIGTH |
| SEC 4.18.2, CLEAR FLR SPACE SEC 4.18.3 |
| NEW COMMENTS DATED 11-18-01PES |
| (1) SHT A1.4 TEACHERS PLANNING RM OR |
| ( BREAK RM.) SEC 4.24 SINK HGTH, 34"FF |
| CLEAR FLR SPACE 30"X 48", KNEE CLEARANCE |
| (2) SHT A1.3, RM #102 PROVIDE CODE REFER |
| ENCE, CHILDERNS H/C PLUMBING FIXTURES. |
| FOR DIMENSIONS, GRAB BARS, DOOR SWING. |
| (3) SHT A2.1,2 PARAPET DETAIL, PROVIDE |
| CALCULATIONS FOR SCUPPER DRAINS, SIZE |
| LOCATION, 1/2 THE VERTICAL WALLS 1108.3 |
| SEE TAB 1109.3, RATE OF RAINFALL 8.5" |
| (4) SHT P-2 RM 401,501 JANITORS CLOSET |
| SPRINKLER HEAD, COMPLY WITH SEC 606.3 & |
| 606.1 ADEQUATE PROTECTION OF POTABLE |
| WATER SHALL BE PROVIDED FROM UNSAFE |
| SYSTEM TO A SAFE SYSTEM, PROVIDE INFOR- |
| MATION ON TYPE OF BACKFLOW PROTECTION. |
| (5A)SHT P-3 WASTE & VENT RISER,TAB 714.1 |
| PROVIDE FIX UNIT LOAD TO SIZE BLDG DRAIN |
| (5B) TWO WAY CO. REQUIRED AT JUNCTION OF |
| BUILDING DRAIN AND THE BUILDING SEWER. |
| SEC 710(6). |
| (6) SHT P-3,4 DETAILS OF WATER PIPING, |
| COMPLY W.SEC 607.8.1,WATER HAMMER ARREST |
| ORS SHALL BE SIZED AND INSTALLED AS PER |
| PDI-WH201, NOT AT THE HIGH POINT OF THE |
| SYSTEM.SPECIFY TYPE AND MANFACTURE. |
| END OF COMMENTSPAUL SCHMITZ |