Plan Review Notes For Permit 01070299 |
Permit Number |
01070299 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-11-29 00:00:00 | ********************DENIED************** | | | | | | PLEASE CLARIFY FCU-1 & FCU-2 IN THE | | STAIRWELL.THERE SHALL BE NO | | MECHANICAL EQUIPMENT IN STAIRWELL AS | | PER THE 2000, 101LIFE SAFETY CODE. | | | | PLAN SHEET M-4 - DUCT PENETRATIONS FOR | | ONE HOUR WALL NOTE 1, DUCTS ARE 100 | | SQUARE INCHES IN AREA OR SMALLER. | | PLEASE CLARIFY WHAT PENETRATIONS ARE | | LESS THAN 100 SQ INCHES.PLEASE NOTE, | | NOT ALL DUCTS ARE IDENTIFIED WITH A | | DUCT SIZE. | | | | PLEASE NOTE EXHAUST OUTLETS FOR DUCTS | | CONVEYING NOXIOUS GASES FLAMMABLE | | VAPORS, AND CORROSIVE VAPORS SHALL | | TERMIATE OUTSIDE THE BUILDING AND SHALL | | BE LOCATED 10' FROM ANY ADJACENT | | BUILDING, PARKING AREA, ADJACENT | | PROPERTY LINE, WINDOW, DOOR, OR AIR | | INTAKE OPENING AND SHALL BE LOCATED AT | | LEAST 10' ABOVE THE ADJOINING GRADE | | LEVEL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|