2001-11-29 00:00:00********************DENIED**************
  
  
 PLEASE CLARIFY FCU-1 & FCU-2 IN THE
 STAIRWELL.THERE SHALL BE NO
 MECHANICAL EQUIPMENT IN STAIRWELL AS
 PER THE 2000, 101LIFE SAFETY CODE.
  
 PLAN SHEET M-4 - DUCT PENETRATIONS FOR
 ONE HOUR WALL NOTE 1, DUCTS ARE 100
 SQUARE INCHES IN AREA OR SMALLER.
 PLEASE CLARIFY WHAT PENETRATIONS ARE
 LESS THAN 100 SQ INCHES.PLEASE NOTE,
 NOT ALL DUCTS ARE IDENTIFIED WITH A
 DUCT SIZE.
  
 PLEASE NOTE EXHAUST OUTLETS FOR DUCTS
 CONVEYING NOXIOUS GASES FLAMMABLE
 VAPORS, AND CORROSIVE VAPORS SHALL
 TERMIATE OUTSIDE THE BUILDING AND SHALL
 BE LOCATED 10' FROM ANY ADJACENT
 BUILDING, PARKING AREA, ADJACENT
 PROPERTY LINE, WINDOW, DOOR, OR AIR
 INTAKE OPENING AND SHALL BE LOCATED AT
 LEAST 10' ABOVE THE ADJOINING GRADE
 LEVEL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.