Plan Review Notes
Plan Review Notes For Permit 01070299
Permit Number 01070299
Review Stop B
Sequence Number 2
Notes
Date Text
2001-12-06 00:00:00SUMMARY OF CONSULTATION MEETING HELD ON
 12/6/01 REGARDING COMMENT NO 17 OF
 12/3/01 PLAN REVIEW (SEE BELOW):
  
 17) SBC 1004.3.1, SBC 1004.3.2 AND
 SBC 1004.3.5 ACCESSIBLE MEANS OF EGRESS,
 AREAS OF REFUGE:
 WHERE MORE THAN ONE REGULAR MEANS OF
 EGRESS IS REQUIRED, NOT LESS THAN TWO
 ACCESSIBLE MEANS OF EGRESS SHALL BE
 PROVIDED.EACH STAIR WHICH IS TO BE
 CONSIDERED PART OF AN ACCESSIBLE MEANS
 OF EGRESS SHALL EITHER INCORPORATE AN
 AREA OF REFUGE OR BE ACCESSED FROM AN
 AREA OF REFUGE.
2001-12-03 00:00:00 
  
  
 BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC* = STANDARD BUILDING CODE (AMENDMENT
 S)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 FL ENERGY CODE = FLORIDA ENERGY EFFICIEN
 CY CODE FOR BUILDING CONSTRUCTION
  
  
 THE FOLLOWING REVIEW COMMENTS ARE
 NUMBERED AS PER THE RELEVANT ITEM FROM
 THE 8/10/01 BUILDING PLAN REVIEW AND THE
 LETTER OF RESPONSE DATED 10/24/01:
  
 3) SBC* 1804.2.7.2(3)NO SOILS REPORT
 WAS ATTACHED TO THE LETTER OF RESPONSE.
  
 7) SHEET S-4. DESIGN PARAMETERS.
 REFERENCE TO SBC 1999 SHALL BE CORRECTED
 TO READ SBC 1997.
  
 8) FL ENERGY CODE 103.0ENERGY CODE
 COMPLIANCE FORMS SHALL BE SUBMITTED AND
 A CERTIFICATE OF COMPLIANCE SHALL BE
 SUBMITTED.
  
 9) PRODUCT APPROVALS.AS PREVIOUSLY
 STATED, THE PERMIT CANNOT BE ISSUED
 UNTIL THE REQUIRED PRODUCT APPROVAL TEST
 REPORTS ARE SUBMITTED. ALTERNATIVELY,
 THE REPORTS CAN BE SUBJECT TO A SEPERATE
 PERMIT APPLICATION WITH ASSOCIATED FEES.
  
 13) SBC 1007.5.5HANDRAILS SHALL
 CONTINUE TO SLOPE BEYOND THE BOTTOM
 RISER BY A DISTANCE EQUAL TO THE DEPTH
 OF ONE TREAD.ON SHEET A5-3, THE 1ST
 FLOOR PLANS 01 AND 02 DO NOT SHOW
 HANDRAILS EXTENDING THE REQUIRED
 DISTANCE BEYOND THE BOTTOM RISER.NOTE
 THAT THE REQUIREMENTS OF SBC 1007.4.2 IN
 RESPECT OF LANDING WIDTH MUST BE
 OBSERVED.
  
 14) SBC* 104.1.1A SEPARATE PERMIT
 APPLICATION IS REQUIRED FOR AWNINGS (SEE
 WINDOWS AND DOORS UNDER SBC* 104.1.1)
  
 16) FL ACC CODE 4.3SUBMIT FURTHER
 INFORMATION REGARDING THE WALKWAY LEVELS
 ON THE EXISTING COVERED WALK AND NEW
 WALKWAY/RAMP LEADING TO THE RETAINED
 ONE-STOREY CBS BUILDING.SUBMIT
 INFORMATION REGARDING THE SLOPE AND
 WALKWAY LEVELS LEADING TO THE WEST
 STAIRCASE EXIT DOOR.THE HEIGHT OF THE
 GUARDING TO THE PROPOSED CONCRETE RAMP
 SHALL BE INCREASED TO 36" (SBC 1015.2)
  
 17) SBC 1004.3.1, SBC 1004.3.2.1,
 SBC 1004.3.5 ACCESSIBLE MEANS OF EGRESS,
 AREAS OF REFUGE:
  
 PENDING CONSULTATION WITH
 CAPTAIN MIKE CARSILLO ON
 WEDNESDAY 12/5/01
  
 18) FL ACC CODE 4.5.1ADD NOTES TO THE
 PLANS STATING THAT ALL FLOORING SURFACES
 ARE TO COMPLY WITH THE ABOVE.NOTE THAT
 APPENDIX A (COMMENTARY OF THE AMERICANS
 WITH DISABILITIES ACT ACCESSIBILITY
 GUIDELINES (ADAAG)) A4.5.1 RECOMMENDS A
 MINIMUM STATIC COEFFICIENT OF FRICTION
 OF 0.6 FOR ACCESSIBLE ROUTES AND 0.8 FOR
 RAMPS.