Plan Review Notes
Plan Review Notes For Permit 01070299
Permit Number 01070299
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-27 00:00:00DENIED;
  
 1.SIZE ROOF DRAINS AND SHOW CALCULATIONS
 SEE SPC CHAPTER 11 BASE CALCULATIONS
 4.5" OF RAIN PER HOUR.
 2.SHOW RISER DIAGRAMS FOR ROOF DRAINS
 AND POTABLE WATER.
 3.SHOW CALCULATIONS FOR MINIMUM BATHROOM
 FACILITIES. SEE TABLE 407 IN THE 94
 PLUMBING CODE.
 4.CONDENSATE DRAINS SHALL BE TRAPPED AND
 HOOKED UP DIRECTLY TO A/H UNITS.BACK-
 WATER VALVE IS NOT REQUIRED. CIVIL
 PLANS DO NOT SHOW CONDENSATE. DRAINS
 SHOULD GO TO STORM OR TO A DRY WELL.
 5.PAGE P-1 (PLUMBING FIXTURE SCHEDULE)
 HANDICAP URINALS ARE REQUIRED.FACBC
 SEC 4.22.5.
 6.SANITARY RISER DIAGRAM MISSING FOR
 DRINKING FOUNTAIN ON SECOND FLOOR.
 7.PAGE A1.1 TOILET IN ROOMS 1O1, 102
 AND 104 SHOULD HAVE FACILITIES TO
 WASH HANDS FOR SANITARY REASONS.
 8.SHOW WHEELCHAIR TURNING RADIUS ON
 PLANS. PER.4.2.3 AND 4.22.3.
 9.IF KITCHEN IS SERVING LUNCHES. PLANS
 SHALL BE REVIEW AND APPROVED BY THE
 HOTEL AND RESTAURANT DEPARTMENT. ALSO
 CONTACT RODNEY COMPO IN THE UTILITY
 DEPARTMENT TO SEE IF A GREASE TRAP IS
 REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369