Plan Review Notes For Permit 01070299 |
Permit Number |
01070299 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-27 00:00:00 | DENIED; | | | | 1.SIZE ROOF DRAINS AND SHOW CALCULATIONS | | SEE SPC CHAPTER 11 BASE CALCULATIONS | | 4.5" OF RAIN PER HOUR. | | 2.SHOW RISER DIAGRAMS FOR ROOF DRAINS | | AND POTABLE WATER. | | 3.SHOW CALCULATIONS FOR MINIMUM BATHROOM | | FACILITIES. SEE TABLE 407 IN THE 94 | | PLUMBING CODE. | | 4.CONDENSATE DRAINS SHALL BE TRAPPED AND | | HOOKED UP DIRECTLY TO A/H UNITS.BACK- | | WATER VALVE IS NOT REQUIRED. CIVIL | | PLANS DO NOT SHOW CONDENSATE. DRAINS | | SHOULD GO TO STORM OR TO A DRY WELL. | | 5.PAGE P-1 (PLUMBING FIXTURE SCHEDULE) | | HANDICAP URINALS ARE REQUIRED.FACBC | | SEC 4.22.5. | | 6.SANITARY RISER DIAGRAM MISSING FOR | | DRINKING FOUNTAIN ON SECOND FLOOR. | | 7.PAGE A1.1 TOILET IN ROOMS 1O1, 102 | | AND 104 SHOULD HAVE FACILITIES TO | | WASH HANDS FOR SANITARY REASONS. | | 8.SHOW WHEELCHAIR TURNING RADIUS ON | | PLANS. PER.4.2.3 AND 4.22.3. | | 9.IF KITCHEN IS SERVING LUNCHES. PLANS | | SHALL BE REVIEW AND APPROVED BY THE | | HOTEL AND RESTAURANT DEPARTMENT. ALSO | | CONTACT RODNEY COMPO IN THE UTILITY | | DEPARTMENT TO SEE IF A GREASE TRAP IS | | REQUIRED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT 8369 |
|