Plan Review Notes For Permit 01070299 |
Permit Number |
01070299 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-10 00:00:00 | 1) PLEASE INDICATE PROPOSED OCCUPANT | | LOAD FOR THE ACADEMY. PLEASE INDICATE | | HOURS OF OPERATION AND THE AGES OF | | THE CHILDREN. PLEASE INDICATE WHAT THE | | GRADE AND AGES OF THE CHILDREN ARE | | PLANNED FOR THE SECOND FLOOR. | | 2) PLEASE INDICATE LOCATIONS AND | | DIMENSIONS FOR WINDOWS USED FOR RESCUE | | AND VENTILATION PURPOSES. | | 3) SEVERAL DRAWINGS ARE NOT SEALED. | | 4) PLEASE INDICATE WHAT PROVISIONS HAVE | | BEEN MADE FOR THE PHYSICALLY | | HANDICAPPED. | | 5) ANY JANITOR CLOSETS LIKE 501 ARE | | REQUIRED TO BE FIRE SPRINKLER PROTECTED. | | DOMESTIC WATER CAN BE USED FOR THIS | | PURPOSE. | | 6) NO FIRE HYDRANTS SHOWN ON ELEVATION | | DRAWINGS. | | 7) NO INTERIOR FINISH CLASSIFICATION | | PROVIDED FOR WALLS AND CEILINGS. | | 8) PLEASE PROVIDE MORE DETAILS ON | | RESIDENTIAL RANGE AND HOOD. WHAT IS THIS | | USED FOR. | | 9) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM SYSTEM. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|