Plan Review Notes
Plan Review Notes For Permit 01070299
Permit Number 01070299
Review Stop B
Sequence Number 1
Notes
Date Text
2001-08-09 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070299
 1901 S FLAGLER DR
 CONT: NAVARRO & MAGGARZ
 TEL: (561) 358-4585
  
 SBC= STANDARD BUILDING CODE
 SBC*= STANDARD BUILDING CODE AMENDMENTS
 FL ACC CODE=FLORIDA ACCESSIBILITY CODE
  
 1)- SBC* 104.2.2 SURVEY REQUIRED, SHOW
 THE FLOOR LEVEL OF THE EXISTING BUILDING
  
 2)- FLOOD ZONE THE SITE IS LOCATED IN A
 "A-5" FLOOD ZONE WITH A BASE ELEVATION
 OF 7'-6" CITY CODE REQUIREMENT.
  
 3)- SBC* 1804.2.7.2(3) SOILS REPORT:
 TO INDICATE THE MINIMUM SAFE BEARING
 VALUE.
  
 4)- FL S.S. 481/61G15-23.002 ARCHITECTUR
 AL PLANS FOR PUBLIC RECORDS REQUIRE SIGN
 ED & SEALED PLANS, SEE NO SEAL ON PLUMB-
 ING & MECHANICAL.
  
 5)- SBC TABLE 1004.EGRESS REQUIREMENTS:
 LIFE SAFETY PLAN DOESN,T SHOW OCC.LOADS
 FOR THE FIRST OR SECOND FLOOR. THE FIRST
 FLOOR DOESN,T INDICATE THE OCC. LOAD
 FROM THE EXISTING BUILDING, THE CLASS-
 ROOMS TAKEN WITH THE 20% NET FOR OCC.
 LOAD @ 0.2 (FOOTNOTE 12,DOORS) GIVES THE
 CLEAR OPENING REQUIRED IN INCHES 187".
 5 DOORS @34"(CLEAR) = 170". AGAIN AS
 STATED EARLIER WE DON'T HAVE THE OCCU-
 PANT LOAD OF THE EXISTING BUILDING.
 SECOND FLOOR,THE EXITING ON THE SECO
 ND FLOOR IS A SERIOUS PROBLEM. THERE IS
 A OCC LOAD OF 1002 A REQUIRED 200.4" IS
 REQUIRED FOR CLEAR DOOR WIDTH. THE
 REQUIRED MINIMUM STAIR WIDTH IS 300.6"
 OR 25.05'. THE TOTAL STAIRWELL WIDTH IN-
 DICATED ON THE PLANS FROM THE 2 STAIR-
 WELLS IS 25', THE TOTAL WIDTH OF THE
 STAIRS IS ONLY 12.5' (SWITCHBACK STAIR).
  
 6)- SBC 1021.1: SPECIAL EXIT REQUIREMENT
 WHAT AGE OR GRADE WILL THE CLASSROOMS BE
 USED FOR, FIRST FLOOR, SECOND FLOOR?
 SHOW ON THE LIFE SAFETY PLAN, PLEASE.
  
 7)- SHEET S-4 DESIGN PARAMETERS, THE BOX
 ES FOR BOTH 1999 (1997) AND THE ASCE
 7-95 ARE BOTH CHECKED, THE BUILDING CAN
 BE DESIGNED FOR ONLY ONE CRITERIA.
  
 8)- MISSING ENERGY CALS.
  
 9)- 1606.2.6.2COMPONENTS & CLADDING:
 A) WINDOWS & MULLIONS: WILL REQUIRE 2
 COPIES OF THE TESTING REPORTS,EITHER
 SBCCI OR DADE COUNTY PRODUCT APPROV-
 AL REPORTS. IF THE REPORTS ARE NOT
 PART OF THE PERMIT PACKAGE, A SEPER-
 ATE PERMIT WITH ASSOCIATED FEES WILL
 BE REQUIRED. IF THE WINDOWS HAVE NOT
 PASSED THE LARGE MISSLE IMPACT RESIS
 TANCE TESTING STORM SHUTTERS WILL BE
 REQUIRED, SEE THE CITIES " OFFICIAL
 INTERPRETATION FOR THE IMPLEMENTA-
 TION OF THE HURRICANE MISSLE IMPACT
 PROTECTION STANDARDS. SEE ITEM
 NUMBER 14 OF INTERPRETATION.
 B) EXTERIOR DOORS AND THE ROOF HATCH
 WILL REQUIREPRODUCT TESTING, IF
 THERE IS GLAZED OPENINGS IN THE UNIT
 THEY WILL NEED TO SHOW PRODUCT TEST-
 ING FOR LARGE MISSLE TESTING.
 C) ROOFING; THE ROOFING ASSEMBLY RE-
 QUIRES PRODUCT TESTING FOR THE WIND-
 ZONE THAT THE MATERIALS WILL BE
 USED IN.
  
 10)- THE DOOR SCHEDULE DOESN'T INDICATE
 THE RATING AS PER SBC 705.1.3.2.1.
 FIREDOORS ARE CLASSIFIED AS 3 HR,1 1/2HR
 1HR, 3/4 HR OR 20 MIN.
  
 11)- SBC 705.6 PENETRATIONS OF HORIZON-T
 AL ASSEMBLIES, PROVIDE MANUFACTURES SPEC
  
 12)-SBC 1604.6.1. CONCENTRATED LOADS
 (POINT LOAD) SEE SHEET S-3 / M-6FOR
 LOADING OF CHILLER.NOT INDICATED ON
 S-3.
  
 13)- SHEET A.5.3 DETAILS .03/.04 METAL
 GAURDRAIL DETAIL, SBC 1007.5.5 HANDRAILS
 SHALL EXTEND 12" HORIZONTALLY BEYOND THE
 TOP RISER. AT THE BOTTOM THE HANDRAIL
 WILL BE CONTINUOUS TO SLOPE FOR A DISTAN
 CE OF THE DEPTH OF ONE TREAD FROM THE
 BOTTOM RISER.
  
 14)- SBC 104.2.2. ADDITIONAL INFORMATION
 REQUIRED: AWNINGS WILL REQUIRE A SSEPER-
 ATE PERMIT W/ FEES.
  
 15)- SBC 104.2.2: BRICK VENEER WALL,
 REQUIRES WALL TIES, SEE SEC 1403SBC.
  
 16)- FL ACC CODE 4.3 SHOW AN ACCESSIBILE
 ROUTE FOR THE INTERIOR AND EXTERIOR OF
 BUILDING.
  
 17)- FL ACC CODE 4.3.11 AREA OF RESCUE
 ASSISTANCE, SHOW COMPLIANCE.
  
 18)- FL ACC CODE 4.5.1 FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES AND IN ACCESS-
 IBLE ROOMS AND SPACES INCLUDING FLOORS,
 RAMPS STAIRS, AND CURB RAMPS SHALL BE
 STABLE, FIRM & SLIP-RESISTANT.A STATIC
 COEFFICIENT OF FRICTION OF 0.6 IS RECOM-
 MENDED FOR ACCESSIBLE ROUTE AND 0.8
 FOR RAMPS.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412