Plan Review Notes
Plan Review Notes For Permit 01070198
Permit Number 01070198
Review Stop B
Sequence Number 3
Notes
Date Text
2001-10-24 00:00:00THE LOCATION OF THE TWO STAIR SHAFTS
 DOES NOT MEET THE DISTANCE SEPARATION
 REQUIREMENTS OF SBC 1004.1.1 AS SHOWN
 ON SHEETS A2.03 AND A 2.06.PLEASE
 REVISE AS NECESSARY.
  
 SINCE THE STAIR SHAFTS ARE SHEAR WALLS
 AND THEIR RELOCATION WILL EFFECT THE
 STEEL PLACEMENT OF THE FOUNDATION PAD,
 THIS ISSUE MUST BE RESOLVED BEFORE A
 FOUNDATION PERMIT CAN BE ISSUED.
  
 A THRESHOLD INSPECTOR IS REQUIRED AND
 IMPACT FEES MUST BE PAID TO THE COUNTY
 AS CITED IN THE EARLIER CHECKLIST(S) AND
 DEMONSTRATION OF COMPLIANCE WITH SBC
 1803.2.