Plan Review Notes For Permit 01070198 |
Permit Number |
01070198 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-09-24 00:00:00 | 1) ELECTRONIC SWITCHES WILL BE REQUIRED | | ON THE O.S.& Y VALVES. | | 2) SINCE THE BUILDING IS A HIGH-RISE | | BUILDING, TWO FIRE DEPARTMENT | | CONNECTIONS WILL BE REQUIRED. NO FIRE | | HYDRANTS SHOWN ON PLANS. ACCORDING TO | | EVAN ROSENBLATT OF SUFFOLK, FIRE | | HYDRANTS ARE LOCATED ON THE NORTH | | SIDE OF THE BUILING. HE WAS ADVISED THAT | | THE FDC'S ARE TO BE WITHIN 150 FEET OF | | FIRE HYDRANTS. | | ACCORDING TO MR. ROSENBLATT, NO GAS | | SERVICE WILL BE PROVIDED. | | 3) PLEASE BE ADVISED THAT 50 PERCENT | | OF THE EXITS ARE REQUIRED TO DISCHARGE | | DIRECTLY TO THE EXTERIOR EXCLUSIVE OF | | HORIZONTAL EXITS. | | 4) A TEMPORARY STANDPIPE WILL BE | | REQUIRED FOR THE BUILDING WHEN IS IS | | UNDER CONSTRUCTION. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|