Plan Review Notes
Plan Review Notes For Permit 01070198
Permit Number 01070198
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-09-24 00:00:001) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON THE O.S.& Y VALVES.
 2) SINCE THE BUILDING IS A HIGH-RISE
 BUILDING, TWO FIRE DEPARTMENT
 CONNECTIONS WILL BE REQUIRED. NO FIRE
 HYDRANTS SHOWN ON PLANS. ACCORDING TO
 EVAN ROSENBLATT OF SUFFOLK, FIRE
 HYDRANTS ARE LOCATED ON THE NORTH
 SIDE OF THE BUILING. HE WAS ADVISED THAT
 THE FDC'S ARE TO BE WITHIN 150 FEET OF
 FIRE HYDRANTS.
 ACCORDING TO MR. ROSENBLATT, NO GAS
 SERVICE WILL BE PROVIDED.
 3) PLEASE BE ADVISED THAT 50 PERCENT
 OF THE EXITS ARE REQUIRED TO DISCHARGE
 DIRECTLY TO THE EXTERIOR EXCLUSIVE OF
 HORIZONTAL EXITS.
 4) A TEMPORARY STANDPIPE WILL BE
 REQUIRED FOR THE BUILDING WHEN IS IS
 UNDER CONSTRUCTION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910