Plan Review Notes For Permit 01070198 |
Permit Number |
01070198 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-08-01 00:00:00 | PLUMBING PLAN REVIEW FOUNDATION PERMIT | | DENIED. | | (1) INFORMATION NEEDED TO REVIEW PLANS | | FOR A FOUNDATION PERMIT ONLY. | | (A) SHT'S S-01.02,P-1,P-2. | | (A) GARAGE DRAINS: TOTAL LOAD FROM UPPER | | FLOORS, SQUARE FOOTAGE,PIPE SIZES. | | (B)SANITARY SEWER: TOTAL LOAD IN FIXTURE | | UNITS,FROM UPPER FLOORS.WITH PIPE SIZES. | | (C) COMMON A/C CONDENSATE SYSTEM: LOAD | | FROM UPPER FLOORS WITH PIPE SIZES. | | CONNECT TO STORM DRAIN OUTSIDE OF BUILD- | | ING WITH A RELIEF VENT.MCWPC-94/804.4(6) | | (D) OIL SEPERATOR SIZED FOR LOAD ON | | SYSTEM,TO BE APPR BY WPB.ENGINEERING. | | (E) BACKFLOW PREVENTER LOCATION IN BUILD | | ING TO BE APPROVED BY WPB UTILITIES DEPT | | (F) IF ANY OF THE ABOVE COMMENTS ARE NOT | | IN THE FOUNDATION,PLEASE INDICATE WERE | | THEY ARE LOCATED IN THE BUILDING. | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS561-659-8096X8233 |
|