Plan Review Notes
Plan Review Notes For Permit 01070198
Permit Number 01070198
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-07-09 00:00:001) NO UNDEGROUND UTILITIES SHOWN
 ON DRAWINGS. ARE GAS, ELECTRIC, WATER,
 SEWER, OR FIRE PROTECTION LINES PRESENT.
 2) NO FIRE HYDRANTS SHOWN ON THE
 DRAWINGS.
 3) WHERE ARE FUTURE CONNECTIONS TO
 THE CITY WATER SUPPLY FOR FIRE
 PROTECTION TO BE MADE.
 4) COULD NOT LOCATE FIRE PUMP OR
 LOCATION OF PROPOSES FIRE PUMP. WHERE
 WILL THE FIRE PROTECTION SERVICE ENTER
 THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910