Plan Review Notes
Plan Review Notes For Permit 01070198
Permit Number 01070198
Review Stop B
Sequence Number 1
Notes
Date Text
2001-07-31 00:00:00A SITE PLAN IS NECESSARY TO LOCATE THE
 BUILDING ON THE PROPERTY.
  
 THE 14" DIA. AUGERCAST PILE DEPTHS WILL
 EXCEED 30 TIMES THEIR DIAMETER AND MUST
 BE INSTALLED UNDER THE DIRECT
 SUPERVISION OF AN ENGINEER.PLEASE
 PROVIDE AFFIRMATION OF THIS.SEE SBC
 1809.2.2.
  
 SHEET S16 "SPECIALTY ENGINEERING NOTES"
 CITES THE SFBC AS DOES S17 UNDER
 STRUCTURAL LOADING.PROVIDE
 AFFIRMATION THAT THE DESIGN WILL COMPLY
 WITH SBCCI, 1997 AND ASCE 7-95.PLEASE
 PROVIDE A COPY OF THE WIND TUNNEL
 TESTING AND THE SOIL INVESTIGATION
 RECOMMENDATIONS.
  
 PROVIDE A THRESHOLD INSPECTION PLAN AND
 CONTACT DON NEELY ASSISTANT BUILDING
 OFFICIAL TO COORDINATE THE THRESHOLD
 INSPECTOR.561-659-8096 X 8333.
  
 PLEASE PROVIDE A DETAIL OR WRITTEN
 NARRATIVE ON THE METHOD OF INSTALLING
 THE AUGER CAST THROUGH THE 5' THICK
 FOUNDATION MAT AS SHOWN IN SECTION 5/S2.
  
 SHEET S17 THE LIVE LOADS ARE NOT CLEAR,
 (TYPO)THE PLYWOOD ROOF SHEATHING SHOWN
 IS NOT ALLOWED IN TYPE I OR II
 CONSTRUCTION.SEE SBC 603 & 604.
  
 SHOW THE DESIGN FOUNDATION CAPACITY AND
 HOW IT WAS DETERMINED.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THEM AND A COPY OF THE RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.