Plan Review Notes
Plan Review Notes For Permit 01070176
Permit Number 01070176
Review Stop B
Sequence Number 1
Notes
Date Text
2001-07-17 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070176
 400 COLUMBIA DR SUITE 111
 CONT : CATALFUMO
 PHONE: 694-3000 X 256
  
 1)- SBC 1004.1.4 ARRANGEMENTS OF EXITS:
 WHERE 2 OR MORE EXITS OR EXIT ACCESS
 DOORS ARE REQUIRED, THE DOORS SHALL BE
 PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN ONE HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE BUILDING OR SPACE. FROM DOOR 103A TO
 DOOR 110B THIS MEASUREMENT MEETS THIS
 CRITERIA BUT SBC 1001.1.3 WILL NOT ALLOW
 A MEANS OF EGRESS TO GO THROUGH KITCHENS
 CLOSETS,(STORAGE ROOMS) NOR RESTROOMS.
  
 2)- DOOR 101C DOESN'T MEET THE MANEUVER-
 ING CLEARENCES AT DOORS FL ACCES CODE
 4.13.6 SEE ATTACHMENT.
  
 3)- ROOMS 110/111 SBC 1204.2 THE WALLS
 AND FLOORS OF ALL PUBLIC RESTROOMS SHALL
 BE LINED WITH AN NONABSORBENT MATERIAL
 TO A HEIGTH OF 4'-0" ABOVE THE FLOOR.
  
 4)- FL ACCES CODE 4.5 FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES AND IN ACCESSIBL
 E ROOMS AND SPACES INCLUDING FLOORS,
 WALKS AND RAMPS SHALL BE STABLE, FIRM &
 SLIP-RESISTANT. ADDAAG A-5. A STATIC
 COEFFICIENT OF FRICTION OF 0.6 IS
 RECOMMENDED FOR ACCESSIBLE ROUTES &
 0.8 FOR RAMPS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412