Plan Review Notes For Permit 01070171 |
Permit Number |
01070171 |
|
Review Stop |
FIRE |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2002-03-01 00:00:00 | A) THE REQUIRED FIRE ALARM SYSTEMS ARE | | TO BE PERMITTED SEPARATELY. PLANS, CUT | | SHEETS, WIRING DIAGRAMS, AND BATTERY | | CALCULATIONS ARE TO BE PROVIDED. MANUAL | | PULL STATIONS AND HORN STROBES ARE TO | | BE PROVIDED THROUGHOUT THE BUILDING. | | ON 3.1.02 WRITER CONTACTED FELIX | | SIERRA WHO ADVISED THAT THE FIRE | | ALARM CONTROL PANEL WILL BE LOCATED | | IN AN EXTERIOR STORAGEROOM. THE FIRE | | ALARM SYSTEM IS TO BE CLASS A OR FULLY | | ADDRESSABLE. | | B) THE EXIT STAIRS ARE TO BE AT LEAST | | 36" WIDE SINCE OCCUPANT LOADS ARE | | EXPECTED TO BE LESS THAN 50 PERSONS. | | THE MINIMUM HEIGHT OF RISER SHALL BE | | 4", MAXIMUM HEIGHT OF RISER 7", WITH | | THE MINIMUM TREAD DEPTH OF AT LEAST | | 11 INCHES. | | C) ILLUMINATION IS TO BE PROVIDED | | FOR THE MEANS OF EGRESS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|