Plan Review Notes
Plan Review Notes For Permit 01070171
Permit Number 01070171
Review Stop B
Sequence Number 4
Notes
Date Text
2002-01-31 00:00:00FBC 705.1.3 REQUIRES THE FIRE RATED
 WINDOWS, (AND DOORS), TO BE LABELED AND
 LISTED IN ACCORDANCE WITH NFPA 80-95.
  
 THE STORAGE ROOM DOORS SHOWN AS (9) ON
 THE PLAN ARE REQUIRED TO BE RATED [45
 MIN] SINCE THEY ARE WITHIN THE TEN FEET
 WIDE SHADOW OF PROTECTION REQUIRED BY
 FBC 1006.2.4.