Plan Review Notes For Permit 01070171 |
Permit Number |
01070171 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2002-01-31 00:00:00 | FBC 705.1.3 REQUIRES THE FIRE RATED | | WINDOWS, (AND DOORS), TO BE LABELED AND | | LISTED IN ACCORDANCE WITH NFPA 80-95. | | | | THE STORAGE ROOM DOORS SHOWN AS (9) ON | | THE PLAN ARE REQUIRED TO BE RATED [45 | | MIN] SINCE THEY ARE WITHIN THE TEN FEET | | WIDE SHADOW OF PROTECTION REQUIRED BY | | FBC 1006.2.4. |
|