Date |
Text |
2001-12-10 00:00:00 | THE TRUSS LAYOUT STILL CALLS OUT THE |
| ASCE 7-93 AND THE ENGINEERING SHEETS |
| ARE NOT SPECIFIC.THIS CAN BE |
| ADDRESSED SUBSEQUENT TO PERMITTING AND |
| PRIOR TO INSTALLATION. |
| |
| THE ENTRANCE DOORS TO THE UNITS ARE |
| REQUIRED TO BE FIRE RATED BY SBC |
| 1006.2.4, BOTH THE UPPER AND LOWER |
| UNITSARE SUBJECT TO THIS REQUIREMENT. |
| THIS WAS REQUESTED ON THE PREVIOUS |
| CHECKLIST. ALSO, THE WINDOWS IN THE "TEN |
| FEET WIDE SHADOW"SEE THE ATTACHED |
| COPY OF THE SBC CODE COMMENTARY. |
| |
| |
| THE "CHASE" ON SHEET 6/A7.03 MUST |
| COMPLY WITH SBC 705.6.1.2 WITH REGARDS |
| TO THE DRYER, EXHAUST DUCTS, PLUMBING |
| ,ELECTRICAL AND ANY OTHER MATERIALS |
| PENETRATING RATED WALLS OR FLOORS AND |
| NOT CONTAINED IN A FIRE RATED SHAFT. |
| |
| THERE ARE NO ARCHITECTURAL SITE PLANS |
| OR PROPERTY SURVEY(S),OR FINISHED FLOOR |
| ELEVATIONS RELATIVE TO NGVD. |
| |
| THE SKETCHES DATED 11/7/01 BY J. |
| FERNANDEZ-BARQUIN, PE, INVESTIGATE THE |
| HAND AND GUARD RAILS UNDER ONLY ONE |
| CONDITION.AN ANALYSIS WAS NOT |
| REQUESTED BUT A THE DESIGN LOADS TO BE |
| USED IN ACCORDANCE WITH SBC 1608.2. |
| ATTACHED IS AN EXERPT FROM THE SBC CODE |
| COMMENTARY DEPICTING THE LOADS AND |
| THEIR APPLICATION. |
| |
| THIS PROJECT WILL APPARENTLY HAVE 24 |
| BUILDINGS IN TWO SEPARATE LOCATIONS. |
| AS NOTED IN THE FIRST PLAN REVIEW, |
| SEPARATE PERMITS ARE REQUIRED FOR EACH |
| BUILDING.WHAT IS BEING APPLIED FOR |
| WITH THIS APPLICATION? |