Plan Review Notes
Plan Review Notes For Permit 01070171
Permit Number 01070171
Review Stop B
Sequence Number 3
Notes
Date Text
2001-12-10 00:00:00THE TRUSS LAYOUT STILL CALLS OUT THE
 ASCE 7-93 AND THE ENGINEERING SHEETS
 ARE NOT SPECIFIC.THIS CAN BE
 ADDRESSED SUBSEQUENT TO PERMITTING AND
 PRIOR TO INSTALLATION.
  
 THE ENTRANCE DOORS TO THE UNITS ARE
 REQUIRED TO BE FIRE RATED BY SBC
 1006.2.4, BOTH THE UPPER AND LOWER
 UNITSARE SUBJECT TO THIS REQUIREMENT.
 THIS WAS REQUESTED ON THE PREVIOUS
 CHECKLIST. ALSO, THE WINDOWS IN THE "TEN
 FEET WIDE SHADOW"SEE THE ATTACHED
 COPY OF THE SBC CODE COMMENTARY.
  
  
 THE "CHASE" ON SHEET 6/A7.03 MUST
 COMPLY WITH SBC 705.6.1.2 WITH REGARDS
 TO THE DRYER, EXHAUST DUCTS, PLUMBING
 ,ELECTRICAL AND ANY OTHER MATERIALS
 PENETRATING RATED WALLS OR FLOORS AND
 NOT CONTAINED IN A FIRE RATED SHAFT.
  
 THERE ARE NO ARCHITECTURAL SITE PLANS
 OR PROPERTY SURVEY(S),OR FINISHED FLOOR
 ELEVATIONS RELATIVE TO NGVD.
  
 THE SKETCHES DATED 11/7/01 BY J.
 FERNANDEZ-BARQUIN, PE, INVESTIGATE THE
 HAND AND GUARD RAILS UNDER ONLY ONE
 CONDITION.AN ANALYSIS WAS NOT
 REQUESTED BUT A THE DESIGN LOADS TO BE
 USED IN ACCORDANCE WITH SBC 1608.2.
 ATTACHED IS AN EXERPT FROM THE SBC CODE
 COMMENTARY DEPICTING THE LOADS AND
 THEIR APPLICATION.
  
 THIS PROJECT WILL APPARENTLY HAVE 24
 BUILDINGS IN TWO SEPARATE LOCATIONS.
 AS NOTED IN THE FIRST PLAN REVIEW,
 SEPARATE PERMITS ARE REQUIRED FOR EACH
 BUILDING.WHAT IS BEING APPLIED FOR
 WITH THIS APPLICATION?