Plan Review Notes
Plan Review Notes For Permit 01070171
Permit Number 01070171
Review Stop P
Sequence Number 2
Notes
Date Text
2001-10-24 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND 98 DESIGN
 MANUAL
 1) ALL GROUND UNITS SHALL COMPLY WITH
 FHA-98 DESIGN MANUAL SPECIFIED IN 24CFR
 100.205(C)(2)-(3). PLEASE COMPLY WITH
 REQUIREMENTS 1 THRU 7 & SPECIFY SPEC "A"
 AND/OR "B" FOR ALL UNITS.
 2) PAGE A5.01, UNIT A-1 MINIMUM SPACE
 FOR W/C'S IS 2'9". 2'6" IS SHOWN FOR W/C
 OPENING.
 3) PAGE A5.02, UNIT A-1-R MINIMUM SPACE
 FOR W/C 2'9"
 4) PAGE A5.03, UNIT B-1 MINIMUM SPACE
 FOR W/C IS 2'9".
 5) PAGE A5.04, UNIT B-1-R MINIMUM SPACE
 FOR W/C IS 2'9"
 6) PAGE A5.05, UNIT C-1 MINIMUM SPACE
 FOR W/C IS 2'9".
 7) PAGE A5.06, UNIT C-1-R MINIMUM SPACE
 FOR W/C IS 2.9".
 8) PAGE A7.03 DETAIL #10 GRAB BAR REIN-
 FORCEMENT DETAIL. PLEASE SUBMIT A SIGNED
 AND SEALED ENGINEERS CALCULATION FOR
 LOAD PRESSURES. PER SBC SEC 1704 ALLOW-
 ABLE LOADS/STRESS FOR GRAB BARS.
 9) PAGE P-6, WATER RISER DIAGRAMS FOR
 UNITS "C" & "C-REV". WATER HAMMER ARRES-
 TOR FOR 2ND FLOOR TO BE LOCATED BY FIX-
 TURES NOT UP HIGH AS SHOWN.
 10) PAGE T1.01 CALLS FOR IR-1 & IR-2
 IRRIGATION PLANS. NO IRRIGATION PLANS
 FOUND.
 11) PAGE P-1, CALLS FOR RPBF TO BE FOUND
 ON CIVIL DRAWINGS. NO BACKFLOW SHOWN FOR
 EACH BLDG. PLEASE INDICATE BACKFLOW FOR
 EACH BLDG.
 12) VENT THROUGH ROOF SHALL BE 4' MIN.
 FROM EACH FIRE SEPARATION WALL PER SBC-
 97 SEC 704.4(2)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377