2001-10-24 00:00:00 | DENIED |
| REFERENCE: SPC-94 - FHA AMEND 98 DESIGN |
| MANUAL |
| 1) ALL GROUND UNITS SHALL COMPLY WITH |
| FHA-98 DESIGN MANUAL SPECIFIED IN 24CFR |
| 100.205(C)(2)-(3). PLEASE COMPLY WITH |
| REQUIREMENTS 1 THRU 7 & SPECIFY SPEC "A" |
| AND/OR "B" FOR ALL UNITS. |
| 2) PAGE A5.01, UNIT A-1 MINIMUM SPACE |
| FOR W/C'S IS 2'9". 2'6" IS SHOWN FOR W/C |
| OPENING. |
| 3) PAGE A5.02, UNIT A-1-R MINIMUM SPACE |
| FOR W/C 2'9" |
| 4) PAGE A5.03, UNIT B-1 MINIMUM SPACE |
| FOR W/C IS 2'9". |
| 5) PAGE A5.04, UNIT B-1-R MINIMUM SPACE |
| FOR W/C IS 2'9" |
| 6) PAGE A5.05, UNIT C-1 MINIMUM SPACE |
| FOR W/C IS 2'9". |
| 7) PAGE A5.06, UNIT C-1-R MINIMUM SPACE |
| FOR W/C IS 2.9". |
| 8) PAGE A7.03 DETAIL #10 GRAB BAR REIN- |
| FORCEMENT DETAIL. PLEASE SUBMIT A SIGNED |
| AND SEALED ENGINEERS CALCULATION FOR |
| LOAD PRESSURES. PER SBC SEC 1704 ALLOW- |
| ABLE LOADS/STRESS FOR GRAB BARS. |
| 9) PAGE P-6, WATER RISER DIAGRAMS FOR |
| UNITS "C" & "C-REV". WATER HAMMER ARRES- |
| TOR FOR 2ND FLOOR TO BE LOCATED BY FIX- |
| TURES NOT UP HIGH AS SHOWN. |
| 10) PAGE T1.01 CALLS FOR IR-1 & IR-2 |
| IRRIGATION PLANS. NO IRRIGATION PLANS |
| FOUND. |
| 11) PAGE P-1, CALLS FOR RPBF TO BE FOUND |
| ON CIVIL DRAWINGS. NO BACKFLOW SHOWN FOR |
| EACH BLDG. PLEASE INDICATE BACKFLOW FOR |
| EACH BLDG. |
| 12) VENT THROUGH ROOF SHALL BE 4' MIN. |
| FROM EACH FIRE SEPARATION WALL PER SBC- |
| 97 SEC 704.4(2) |
| |
| REVIEW BY KEN STEVENS |