Plan Review Notes
Plan Review Notes For Permit 01070171
Permit Number 01070171
Review Stop B
Sequence Number 2
Notes
Date Text
2001-10-29 00:00:00THE LETTER DATED 8/20/01 FROM JUAN
 FERNANDEZ-BARQUIN, P.E. CALLS OUT WIND
 DESIGN TO ASCE 7-88/93.THE 1997
 STANDARD BUILDING CODE INVOKES ASCE
 7-95.PLEASE REVISE AS NECESSARY AND
 DEMONSTRATE COMPLIANCE WITH SAME.WEST
 PALM BEACH IS IN A 140 MPH ZONE FOR ASCE
 AND 110 MPH IF SBC 1606.2 IS USED.SEE
 SBC 1606.2.2 RE: MIXING OF WIND
 PRESSURES FROM DIFFERENT SOURCES. SHEET
 S11 WRONGLY CITES 100 MPH AND ASCE 7-93.
 MARTINEZ TRUSSES USED ASCE 7-93 AS WELL.
  
  
 THE NOA FOR THE METAL TECH SHUTTERS
 EXPIRED 10/01/01.FURTHER, THE
 COMPONENTS ARE NOT MARKED AS PROVIDED
 FOR IN SECTION 6.1.2 OF THAT REPORT OR
 AN INSTALLATION SCHEDULE INCLUDED.
  
 SEE THE BUILDING OFFICIAL'S
 INTERPRETATION OF HURRICANE MISSILE
 IMPACT REGARDING THE USE OF SHUTTERS ON
 MULTI FAMILY BUILDINGS.A COPY IS
 ATTACHED.
  
 THE ENTRANCE DOORS TO THE UNITS ARE
 REQUIRED TO BE PROTECTED OPENINGS AS
 PROVIDED FOR IN SBC 1006.2.4. THIS IS
 NOT READILY DISCERNIBLE FROM THE DOOR
 SCHEDULE ON SHEET A5.01.ALSO, THE
 WINDOW TYPE [C] IS SHOWN AS AN OPERABLE
 WINDOW.THIS MUST BE A TESTED FIRE
 RATED ASSEMBLY.SEESBC 705.1.3.THE
 WINDOWS SHOWN AS [H] AND THE GLASS BLOCK
 IN THE END "C" UNITS ARE SUBJECT TO
 SBC1006.2.4.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE 1 HR
 SHAFT IN SECTION 6/A7.03.SEE SBC
 701.2.
  
 PLEASE PROVIDE A DIMENSIONED SITE PLAN
 AND A RECENT PROPERTY SURVEY.
  
 SHOW THE FINISH FLOOR ELEVATIONS
 RELATIVE TO NGVD.
  
 SHOW THE HANDRAIL AND GUARDRAIL LOADS AS
 REQUESTED ON THE PREVIOUS CHECKLIST,
 SEE SBC 1608.2.
  
 EACH BUILDING REQUIRES A SEPARTE PERMIT,
 ALSO SEE THE PREVIOUS LIST REGARDING IM
 PACT FEES AND A RESIDENT INSPECTOR.