Plan Review Notes For Permit 01070171
Permit Number 01070171
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-21 00:00:00DENIED;
  
 FAIR HOUSING ACT NOTES
 1.SPECIFY ONE DRAWINGS IF SPECIFICATION
 "A" OR "B" WILL BE USED FOR BATHROOMS
 IN ALL GROUND FLOOR UNITS.
 2.SHOWW CLEAR FLOOR SPACE IN FRONT OF
 PLUMBING FIXTURES AND KITCHEN
 APPLIANCES.
 3.SHOW REINFORCED BACKING IN WALLS FOR
 GRAB BARS TO COMPLY WITH FHA REQUIRE-
 MENT # 6.
 4.SIZE AND CONFIGURATION OF BATHROOMS
 SHALL COMPLY WITH FHA REQUIREMENT #7.
 AT THIS REVIEW NONE OF THE BATHROOMS
 COMPLY.
  
 PLUMBING PLAN REVIEW;
 1.BACKFLOW PROTECTION REQUIRED AT EACH
 BUILDING.
 2.FOUR INCH. SHALL BE WITHIN 3' OF
 BUILDING.
 3.IF WATER HAMMER ARRESTERS ARE
 SPECIFIED BY ENGINEER THEY MUST BE
 ENGINEERED AND COMPLY WITH SPC 607.8.2
 AND 607.8.3.
 4.WHERE IS CHART SHOWING WATER PIPE
 SIZES FOR WATER RIZER DIAGRAMS?
 5.SECOND FLOOR WATER HEATERS REQUIRE A
 PAN WITH DRAIN. PAN DRAIN LINE SHOULD
 BE ONE INCH. COMPLY WITH SPC SEC.
 507.8.2.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369