Plan Review Notes For Permit 01070171 |
Permit Number |
01070171 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-21 00:00:00 | DENIED; | | | | FAIR HOUSING ACT NOTES | | 1.SPECIFY ONE DRAWINGS IF SPECIFICATION | | "A" OR "B" WILL BE USED FOR BATHROOMS | | IN ALL GROUND FLOOR UNITS. | | 2.SHOWW CLEAR FLOOR SPACE IN FRONT OF | | PLUMBING FIXTURES AND KITCHEN | | APPLIANCES. | | 3.SHOW REINFORCED BACKING IN WALLS FOR | | GRAB BARS TO COMPLY WITH FHA REQUIRE- | | MENT # 6. | | 4.SIZE AND CONFIGURATION OF BATHROOMS | | SHALL COMPLY WITH FHA REQUIREMENT #7. | | AT THIS REVIEW NONE OF THE BATHROOMS | | COMPLY. | | | | PLUMBING PLAN REVIEW; | | 1.BACKFLOW PROTECTION REQUIRED AT EACH | | BUILDING. | | 2.FOUR INCH. SHALL BE WITHIN 3' OF | | BUILDING. | | 3.IF WATER HAMMER ARRESTERS ARE | | SPECIFIED BY ENGINEER THEY MUST BE | | ENGINEERED AND COMPLY WITH SPC 607.8.2 | | AND 607.8.3. | | 4.WHERE IS CHART SHOWING WATER PIPE | | SIZES FOR WATER RIZER DIAGRAMS? | | 5.SECOND FLOOR WATER HEATERS REQUIRE A | | PAN WITH DRAIN. PAN DRAIN LINE SHOULD | | BE ONE INCH. COMPLY WITH SPC SEC. | | 507.8.2. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT.8369 |
|