2001-08-07 00:00:00 | *******************DENIED*************** |
| |
| |
| PLEASE PROVIDE THE FOLLOWING INFORMATION |
| FOR REVIEW: |
| |
| 1.PLAN SHEET M-4, DRYER EXHAUST VENTS |
| ARE GREATER THAN 25'.AS PER 1997 |
| SMC 509.3, THE MAXIMUM LENGTH SHALL |
| NOT EXCEED 25' FROM DRYER LOCATION |
| TO WALL OR ROOF CAP.5' REDUCTION |
| FOR EACH 90 DEGREE BEND AND 2 1/2' |
| REDUCTION FOR EACH 45 DEGREE BEND. |
| THE WALL OR ROOF CAP SHALL BE NON- |
| SCREENED WITH BACK DRAFT DAMPER. |
| |
| 2.PLAN SHEET M-6, A/C & E.W.H. DETAIL, |
| AS PER AMENDED 1994 SPC 804.3 #5., |
| CONDENSATE DRAINS SHALL VENT TO THE |
| ATMOSHERE AND NOT TERMINATE IN THE |
| THE WALL AS SHOWN ON THE DETAIL. |
| SHOULD VENT TERMINATE IN THE ATTIC, |
| IS SHALL BE A MINIMUM OF 6" ABOVE |
| THE INSULATION. |
| |
| 3.PLAN SHEET M-6, A/C & E.W.H. DETAIL, |
| INDICATES OVERFLOW PROTECTION SHALL |
| BE ON THE UPPER FLOORS ONLY.THIS |
| IS UNACCEPTABLE, OVERFLOW PROTECTION |
| SHALL BE ON ALL UNITS TO PREVENT |
| DAMAGE TO CARPET, WALLS AND INTERIOR |
| OF APPARTMENT. |
| |
| NOTE:HEIGHT REQUIREMENTS FOR CONTROLS |
| SHALL COMPLY WITH CHAPTER 5 OF |
| FAIR HOUSING ACT. |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CONTACT |
| PATTY KRAUSS AT 659-8096 EXT. 8388. |