2001-07-09 00:00:00 | |
| |
| |
| |
| |
| |
| |
| |
| ARE THE BUILDING PLANS THE SAME FOR |
| SUBDIVISION 3A AND 3B. |
| |
| PLAN REVIEW COMMENTS FOR BUILDINGS. |
| 1) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR ENTRY GATES. WHAT PROVISIONS HAVE |
| BEEN MADE FOR FIRE AND PARAMEDICAL |
| ACCESS INTO THE COMPLEX. ARE THE |
| SECURITY GATES EQUIPPED WITH EMERGENCY |
| POWER SHOULD LOSS OF POWER OCCURS. |
| MINIMUM ACCESS TO BE AT LEAST 20 FEET |
| IN CLEAR WIDTH. |
| 2) PLEASE BE ADVISED THAT CITY CODE |
| SECTION 11-4 REQUIRES THAT NOT ITEMS |
| BE PLACED WITHIN 18 FEET OF FIRE |
| HYDRANTS. ALSO WET FIRE HYDRANTS ARE |
| REQUIRED PRIOR TO, DURING AND AFTER |
| CONSTRUCTION. |
| 3) BUILDING ADDRESSES REQUIRED PER CITY |
| CODE 3343-00. |
| 4) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| 8X8 GLASS BLOCKS FOR THE ONE HOUR FIRE |
| RATING SHOWN ON PAGE A2.0.1. |
| 5) COULD NOT LOCATE FIRE HYDRANT |
| LOCATIONS FOR SUBDIVISION 3B ON WATER |
| AND SEWER PLANS. |
| 6) BUILDINGS ARE REQUIRED TO HAVE FIRE |
| ALARM SYSTEMS IF THEY ARE THREE STORIES |
| OR MORE OR IF THEY CONTAIN ELEVEN |
| LIVING UNITS. SEPARATE PLANS AND PERMITS |
| REQUIRED FOR THESE CLASS A OR FULLY |
| ADDRESSABLE FIRE ALARM SYSTEMS. |