2001-07-10 00:00:00 | FAILED: |
| 1. PLEASE PROVIDE SURVEYING PLANS. |
| 2. PLEASE PROVIDE STORM WATER |
| CALCULATIONS FOR OUR REVIEW AND APPROVAL |
| 3. PLEASE INCLUDE PERVIOUS & IMPERVIOUS |
| CALCULATIONS AREA ON PAVING AND DRAINAGE |
| SHEETS. |
| 4. PLEASE PROVIDE THE STATUS OF APPROVAL |
| FROM THE SFWMD AND DEP IN REGARDS TO |
| THIS PROJECT. |
| 5. PLEASE PROVIDE POLLUTION PREVENTION |
| PLANS, PLANS SHOULD BE INSTALLED IN THE |
| FIELD PRIOR TO ANY EARTH WORKS. |
| 6. PROVIDE IRRIGATION PLANS, A SEPARATE |
| BACKFLOW PREVENTERS IS RECOMMENDED. |
| 7. SHOW LOCATIONS FOR BACKFLOW |
| PREVENTERS AND DOUBLE CHECK ASSEMBLIES. |
| 8. SHOW SAMPLE POINTS LOCATIONS. |
| 9. PLEASE PROVIDE DETAILS FOR DUMPSTER |
| ENCLOSURES, SEE ATTACHED. |
| 10. ANY NEW CONNECTIONS TO CITY SERVICES |
| REQUIRES A SEPARATE PERMITT AND APPROVAL |
| FROM PUBLIC UTILITIES ENGINEERING |
| SERVICES DEPARTMENT. 659-8040 |
| 11. ANY WORK WITHIN PUBLIC R.O.W |
| REQUIRES PERMITT FROM COUNTY OR CITY |
| ENGINEERS OFFICE. 659-8040 |
| |
| 3A - SECTION |
| 1. PLEASE SHOW THE ROADWAY ENTRANCE / |
| DETAILS, A MINIMUM OF 20'-0" CLEAR IS |
| REQUIRED FOR FIRE TRUCK TO ENTER THE |
| SITE. |
| |
| 3B - SECTION |
| 1. PLEASE SHOW THE WIDTH DIMENSIONS AT |
| THE ENTRANCE, A MINIMUM OF 20'-0" CLEAR |
| IS REQUIRED FOR FIRE TRUCK TO ENTER THE |
| SITE. |
| 2. SHEET 3 OF 5 SHOWS RCP LEAVING |
| STRUCTURE ( BY OTHERS), PLEASE STATE, |
| WHERE THIS IS CONNECTED TO. |
| 3. PLEASE SHOW WATER SERVICE TO BUILDING |
| 15,20 AND 23. SHEET 2,3,4 OF 12 |
| 4. PLEASE SHOW THE FIRE HYDRANTS THROUGH |
| -OUT. |