Plan Review Notes
Plan Review Notes For Permit 01070171
Permit Number 01070171
Review Stop B
Sequence Number 1
Notes
Date Text
2001-07-27 00:00:00THE STRUCTUAL CALCS CITE 40 PSF FOR THE
 STAIRS.THE CITY USES SBC TABLE 1604.1.
 PLEASE REVISE AS NECESSARY.
  
 SEVERAL OF THE PAGES OF THE STRUCTUAL
 CALCS CITE THE UBC WHICH IS NOT
 RECOGNIZED BY THE CITY.
  
 THE CALCULATIONS DO NOT SHOW AN
 INVESTIGATION FOR WINDLOADS.
  
 THE METRO DADE NOA FOR THE STEEL DOOR
 95-1212.01 IS EXPIRED AND THE DRAWING
 IS ILLEGIBLE.
  
 THE INFORMATION FOR THE "PICTURE
 WINDOW"IS NOT A NOTICE OF ACCEPTANCE OR
 TEST REPORT.
  
 THE NOA FOR THE METAL TECH SHUTTERS DOES
 NOT HAVE THE COMPONENTS MARKED OR AN
 INSTALLATION SCHEDULE.
  
 UNIT TYPE A1 SHOWS A DOOR WITH A
 SIDELITE AND NO ACCOMPANYING PRODUCT
 REPORT.
  
 THE GLAZING ADJACENT THE ENTRY DOORS OF
 THE B TYPE UNITS MUST COMPLY WITH SBC
 2405.2.1.
  
 SEE SBC 1006.2.4 FOR OPENING PROTECTION
 REQUIREMENTS IN THE VICINITY OF THE
 STAIRS.
  
 THE GUARDRAIL SHOWN IN SECTION 8/A701
 DOES NOT HAVE THE 2" SPHERE TOE RAIL
 REQUIREMENT OF SBC 1015.3.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE 1
 HOUR CHASE DEPICTED IN SECTION 6/A7.03.
  
 THE PROPERTY MAY BE IN A FLOOD ZONE BUT
 IN THE ABSENCE OF A SURVEY OR LEGAL
 DESCRIPTION, IT CANNOT BE DETERMINED.
  
 THE NOTES ON SHEET S1 CALL OUT A SOIL
 PRESSURE OF 2000 PSF AND S11 3000 PSF.
 PLEASE CLARIFY.
  
 S12 DOES NOT SHOW ANY WIND PRESSURES FOR
 THE ROOF.
  
 SHOW THE DESIGN LOADS FOR THE HANDRAILS
 AND GUARDRAILS, INCLUDING THE LATICE, IN
 ACCORDANCE WITH SBC 1608.2.
  
 STRUCTURAL. WHAT IS THE BASE VELOCITY
 PRESSURE USED?ASCE OR SBC?
  
 THE A 5 SHEETS REFERENCE A TYPICAL
 TENANT SEPARATION WALL TO BE 4/A601 AND
 IS NOT FOUND THERE.IS IT 1/A6.02?
 NOTE, THIS DOES NOT MEET THE DEFINITION
 OF A TOWNHOUSE. SEE SBC 202.
  
  
 A SCALED AND DIMENSIONED SITE PLAN WAS
 NOT INCLUDED SO COMPLIANCE WITHSBC
 TABLE 600 CANNOT BE DETERMINED.IT
 APPEARS FROM THE LANDSCAPE PLANS THAT
 THE STAIRS MAY NOT COMPLY WITH SBC
 1006.2.2.
  
 SHOW A STAIR DETAIL SO THAT COMPLIANCE
 WITH SBC 1007.3.1 MAY BE DETERMINED.
  
 SHOW THE FIRE SPRINKLER DESIGN AS
 REQUIRED BY FS 553.79 (2)
  
 INCLUDE THE REINFORCED MASONRY CHECKLIST
 REQUIRED BY ACI 530.
  
 A RESIDENT INSPECTOR WILL BE REQUIRED
 FOR THIS PROJECT.CONTACT DON NEELY AT
 561-659-8096X 8333 FOR MORE
 INFORMATION.
  
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY FOR THE CITY.CALL
 561-233-5025
 FOR MORE INFORMATION.