2001-07-27 00:00:00 | THE STRUCTUAL CALCS CITE 40 PSF FOR THE |
| STAIRS.THE CITY USES SBC TABLE 1604.1. |
| PLEASE REVISE AS NECESSARY. |
| |
| SEVERAL OF THE PAGES OF THE STRUCTUAL |
| CALCS CITE THE UBC WHICH IS NOT |
| RECOGNIZED BY THE CITY. |
| |
| THE CALCULATIONS DO NOT SHOW AN |
| INVESTIGATION FOR WINDLOADS. |
| |
| THE METRO DADE NOA FOR THE STEEL DOOR |
| 95-1212.01 IS EXPIRED AND THE DRAWING |
| IS ILLEGIBLE. |
| |
| THE INFORMATION FOR THE "PICTURE |
| WINDOW"IS NOT A NOTICE OF ACCEPTANCE OR |
| TEST REPORT. |
| |
| THE NOA FOR THE METAL TECH SHUTTERS DOES |
| NOT HAVE THE COMPONENTS MARKED OR AN |
| INSTALLATION SCHEDULE. |
| |
| UNIT TYPE A1 SHOWS A DOOR WITH A |
| SIDELITE AND NO ACCOMPANYING PRODUCT |
| REPORT. |
| |
| THE GLAZING ADJACENT THE ENTRY DOORS OF |
| THE B TYPE UNITS MUST COMPLY WITH SBC |
| 2405.2.1. |
| |
| SEE SBC 1006.2.4 FOR OPENING PROTECTION |
| REQUIREMENTS IN THE VICINITY OF THE |
| STAIRS. |
| |
| THE GUARDRAIL SHOWN IN SECTION 8/A701 |
| DOES NOT HAVE THE 2" SPHERE TOE RAIL |
| REQUIREMENT OF SBC 1015.3. |
| |
| SHOW THE FIRE DESIGN NUMBER FOR THE 1 |
| HOUR CHASE DEPICTED IN SECTION 6/A7.03. |
| |
| THE PROPERTY MAY BE IN A FLOOD ZONE BUT |
| IN THE ABSENCE OF A SURVEY OR LEGAL |
| DESCRIPTION, IT CANNOT BE DETERMINED. |
| |
| THE NOTES ON SHEET S1 CALL OUT A SOIL |
| PRESSURE OF 2000 PSF AND S11 3000 PSF. |
| PLEASE CLARIFY. |
| |
| S12 DOES NOT SHOW ANY WIND PRESSURES FOR |
| THE ROOF. |
| |
| SHOW THE DESIGN LOADS FOR THE HANDRAILS |
| AND GUARDRAILS, INCLUDING THE LATICE, IN |
| ACCORDANCE WITH SBC 1608.2. |
| |
| STRUCTURAL. WHAT IS THE BASE VELOCITY |
| PRESSURE USED?ASCE OR SBC? |
| |
| THE A 5 SHEETS REFERENCE A TYPICAL |
| TENANT SEPARATION WALL TO BE 4/A601 AND |
| IS NOT FOUND THERE.IS IT 1/A6.02? |
| NOTE, THIS DOES NOT MEET THE DEFINITION |
| OF A TOWNHOUSE. SEE SBC 202. |
| |
| |
| A SCALED AND DIMENSIONED SITE PLAN WAS |
| NOT INCLUDED SO COMPLIANCE WITHSBC |
| TABLE 600 CANNOT BE DETERMINED.IT |
| APPEARS FROM THE LANDSCAPE PLANS THAT |
| THE STAIRS MAY NOT COMPLY WITH SBC |
| 1006.2.2. |
| |
| SHOW A STAIR DETAIL SO THAT COMPLIANCE |
| WITH SBC 1007.3.1 MAY BE DETERMINED. |
| |
| SHOW THE FIRE SPRINKLER DESIGN AS |
| REQUIRED BY FS 553.79 (2) |
| |
| INCLUDE THE REINFORCED MASONRY CHECKLIST |
| REQUIRED BY ACI 530. |
| |
| A RESIDENT INSPECTOR WILL BE REQUIRED |
| FOR THIS PROJECT.CONTACT DON NEELY AT |
| 561-659-8096X 8333 FOR MORE |
| INFORMATION. |
| |
| |
| BEFORE A PERMIT TO CONSTRUCT CAN BE |
| ISSUED IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY FOR THE CITY.CALL |
| 561-233-5025 |
| FOR MORE INFORMATION. |