Plan Review Notes
Plan Review Notes For Permit 01070113
Permit Number 01070113
Review Stop R
Sequence Number 1
Notes
Date Text
2001-07-25 00:00:00CHECKLIST:
 1-FAILED BY PLUMBING. SEE COMMENTS.
 2-FILE NOTICE OF COMMENCEMENT.
 3-FLOOD ZONE AO. WILL NEED ELEVATION
 CERTIFICATE.
 4-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS OR APPLY FOR SEPARATE PERMIT.
 5-CLEARLY INDICATE ON PLANS WHICH OPTION
 IS GOING TO BE BUILT. CROSS OUT THE
 ONES THAT DON'T APPLY.
 -PROVIDE THE CORRESPONDING PRODUCT
 APPROVALS FOR SELECTED OPTIONS.
 6-PRELIMINARY SOIL TEST RECOMMENDS SOIL
 TEST FOR EACH STRUCTURE. FOLLOW THESE
 RECOMMENDATIONS AND PROPER PREPARATION
 OF SOIL.
 7-ENERGY CALCULATIONS AND ARCHITECTURAL
 PLANS DON'T MATCH. HOT WATER HEATER
 CAPACITY IS 40 GALS OR 50 GALS. REVISE
 EITHER ONE TO MATCH.
 8-PROVIDE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM.
 9-DESIGNER OF RECORD TO REVIEW ALL TRUSS
 DRAWINGS (AFTER THEY ARE REVISED FOR
 ASCE 7-95 FOR 145MPH WIND LOAD) AND
 SPECIFY CONNECTORS THAT WILL RESIST
 THE ENGINEERED CALCULATED LOADS FOR
 EACH TRUSS.
  
  
  
  
 NOTES:
 -THESE COMMENTS APPLY FOR PERMIT #S:
 01070113, 01070110, 01070104 AND
 01070106.
 -ALL DRAWINGS WILL BE FILED UNDER
 PERMIT #01070113.