Date |
Text |
2001-07-25 00:00:00 | CHECKLIST: |
| 1-FAILED BY PLUMBING. SEE COMMENTS. |
| 2-FILE NOTICE OF COMMENCEMENT. |
| 3-FLOOD ZONE AO. WILL NEED ELEVATION |
| CERTIFICATE. |
| 4-PROVIDE COMPLETE INFORMATION FOR STORM |
| PANELS OR APPLY FOR SEPARATE PERMIT. |
| 5-CLEARLY INDICATE ON PLANS WHICH OPTION |
| IS GOING TO BE BUILT. CROSS OUT THE |
| ONES THAT DON'T APPLY. |
| -PROVIDE THE CORRESPONDING PRODUCT |
| APPROVALS FOR SELECTED OPTIONS. |
| 6-PRELIMINARY SOIL TEST RECOMMENDS SOIL |
| TEST FOR EACH STRUCTURE. FOLLOW THESE |
| RECOMMENDATIONS AND PROPER PREPARATION |
| OF SOIL. |
| 7-ENERGY CALCULATIONS AND ARCHITECTURAL |
| PLANS DON'T MATCH. HOT WATER HEATER |
| CAPACITY IS 40 GALS OR 50 GALS. REVISE |
| EITHER ONE TO MATCH. |
| 8-PROVIDE THE DESIGN CERTIFICATION FOR |
| BUILDING CODE COMPLIANCE FORM. |
| 9-DESIGNER OF RECORD TO REVIEW ALL TRUSS |
| DRAWINGS (AFTER THEY ARE REVISED FOR |
| ASCE 7-95 FOR 145MPH WIND LOAD) AND |
| SPECIFY CONNECTORS THAT WILL RESIST |
| THE ENGINEERED CALCULATED LOADS FOR |
| EACH TRUSS. |
| |
| |
| |
| |
| NOTES: |
| -THESE COMMENTS APPLY FOR PERMIT #S: |
| 01070113, 01070110, 01070104 AND |
| 01070106. |
| -ALL DRAWINGS WILL BE FILED UNDER |
| PERMIT #01070113. |