Plan Review Notes For Permit 01061355 |
Permit Number |
01061355 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-07-24 00:00:00 | PLUMBING PLAN REVIEW DENIED,2ND TIME | | PLEASE ADDRESS PREVIOUS COMMENTS,7-7-01 | | (1) SHT-1 COMPLY W/SEC 407.1.3 MINIMUM | | FACILITIES:USE TAB 407 TO CACULATE THE | | NUMBER OF FIXTURES FOR THE MEN,WOMEN'S | | REST RM'S BASED ON SQUARE FOOTAGE. | | (2) COMPLY W/FACBC SEC 4.1.8.3 URINALS, | | URINAL TO BE CENTERED IN THE 30"X 48" | | CLEAR FLOOR SPACE. | | (3) BREAK ROOM SINK COMPLY W/FACBC SEC. | | 4.24.5 CLEAR FLR SPACE IN FRONT OF SINK, | | FRONT OR SIDE APPROACH. | | SEC 4.24.2 HIGHT OF COUNTER, 34" AFF. | | SEC 4.24.3 KNEE CLEARANCE, 27" HIGH, | | 30" WIDE, & 19" DEEP SHALL BE PROVIDED | | UNDER SINK. | | (4)SHT-5, WTR HTR TO BE READLY ACESSIBLE | | SEC 501.7,SHOW A DETAIL OF HOW THIS WILL | | BE BE DONE IN A CABNET. | | (5) DWV ISOMETRIC,URI & LAV,ON A CROSS. | | 2-LAV'S TIED TOGETHER ON 2 WASTE RISERS. | | (6) TRAP PRIMERS REQ.ON F/D'S IN PUBLIC | | REST RM'S,SEC 409.4 | | (7)SHT-5,WATER RISER: COMPLY W/SEC 607.8 | | NOTE #12 REFERES TO AIR CHAMBERS,NOT APP | | ROVED IN CEILING AS WELL AS WATER HAMMER | | ARRESTORS. PROVIDE MFG INSTRUCTIONS ON | | SIZE AND PLACEMENT. | | END OF COMMENTSPAULSCHMITZ | | QUESTIONS561-659-8096X8233 |
|