Plan Review Notes
Plan Review Notes For Permit 01061355
Permit Number 01061355
Review Stop P
Sequence Number 2
Notes
Date Text
2001-07-24 00:00:00PLUMBING PLAN REVIEW DENIED,2ND TIME
 PLEASE ADDRESS PREVIOUS COMMENTS,7-7-01
 (1) SHT-1 COMPLY W/SEC 407.1.3 MINIMUM
 FACILITIES:USE TAB 407 TO CACULATE THE
 NUMBER OF FIXTURES FOR THE MEN,WOMEN'S
 REST RM'S BASED ON SQUARE FOOTAGE.
 (2) COMPLY W/FACBC SEC 4.1.8.3 URINALS,
 URINAL TO BE CENTERED IN THE 30"X 48"
 CLEAR FLOOR SPACE.
 (3) BREAK ROOM SINK COMPLY W/FACBC SEC.
 4.24.5 CLEAR FLR SPACE IN FRONT OF SINK,
 FRONT OR SIDE APPROACH.
 SEC 4.24.2 HIGHT OF COUNTER, 34" AFF.
 SEC 4.24.3 KNEE CLEARANCE, 27" HIGH,
 30" WIDE, & 19" DEEP SHALL BE PROVIDED
 UNDER SINK.
 (4)SHT-5, WTR HTR TO BE READLY ACESSIBLE
 SEC 501.7,SHOW A DETAIL OF HOW THIS WILL
 BE BE DONE IN A CABNET.
 (5) DWV ISOMETRIC,URI & LAV,ON A CROSS.
 2-LAV'S TIED TOGETHER ON 2 WASTE RISERS.
 (6) TRAP PRIMERS REQ.ON F/D'S IN PUBLIC
 REST RM'S,SEC 409.4
 (7)SHT-5,WATER RISER: COMPLY W/SEC 607.8
 NOTE #12 REFERES TO AIR CHAMBERS,NOT APP
 ROVED IN CEILING AS WELL AS WATER HAMMER
 ARRESTORS. PROVIDE MFG INSTRUCTIONS ON
 SIZE AND PLACEMENT.
 END OF COMMENTSPAULSCHMITZ