2001-07-09 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT UNDER 230-2
 A SEPARATE SERVICE IS NOT PERMITTED.
 TO HAVE A SEPARATE SERVICE THE SPACE
 WOULD HAVE TO HAVE A 2HR SEPARATION FOR
 BUILDING REQMENTS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS FOR NEW
 MAIN DISCONNECTS.
  
 3)NOTE: PLEASE NOTE THAT PERMIT APPLICA-
 -TION MENTIONS A NEW SUB-PANEL BUT NOTH-
 -ING IS SHOWNON RISER DIAGRAM.?
 PLEASE CLARIFY.
  
 4)NOTE: PLEASE PROVIDE CLARIFICATION
 ON RISER SHOWING AN 800A OVERHEAD DROP
 TO A 1200A SERVICE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372