Plan Review Notes For Permit 01061355 |
Permit Number |
01061355 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-09 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT UNDER 230-2 | | A SEPARATE SERVICE IS NOT PERMITTED. | | TO HAVE A SEPARATE SERVICE THE SPACE | | WOULD HAVE TO HAVE A 2HR SEPARATION FOR | | BUILDING REQMENTS. | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | PLEASE NOTE THAT AIC RATINGS FOR NEW | | MAIN DISCONNECTS. | | | | 3)NOTE: PLEASE NOTE THAT PERMIT APPLICA- | | -TION MENTIONS A NEW SUB-PANEL BUT NOTH- | | -ING IS SHOWNON RISER DIAGRAM.? | | PLEASE CLARIFY. | | | | 4)NOTE: PLEASE PROVIDE CLARIFICATION | | ON RISER SHOWING AN 800A OVERHEAD DROP | | TO A 1200A SERVICE? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|