Plan Review Notes
Plan Review Notes For Permit 01061269
Permit Number 01061269
Review Stop P
Sequence Number 2
Notes
Date Text
2001-09-10 00:00:00DENIED..
  
 REFERENCE: SPC-94 - SGC-97
  
 1) PAGE P1 & P2, DRY HORIZONTAL VENT
 SHOWN AFTER BIDET IN BATH #1 NOT ALLOWED
 SPC-94 SECT. 906.2.
  
 2) PAGE P2, DRY HORIZONTAL VENT SHOWN
 AFTER BIDET IN BATH #2 NOT ALLOWED SPC-
 94 SECT. 906.2.
  
 3) PAGE P2, DRY HORIZONTAL VENT SHOWN
 AFTER SHOWER IN BATH #3 NOT ALLOWED SPC-
 94 SECT. 906.2.
  
 4) PAGE P2 SANT. RISER DIAGRAM, CLEAN
 OUT REQUIRED ON WASH MACHINE STACK AT 4'
 ABOVE FINISHED FLOOR. (SANT. RISER DIA-
 GRAM.
  
 5) PAGE P2, SANT. RISER DIAGRAM, A 3"
 VENT THROUGH THE ROOF IS REQUIRED PER
 SPC-94 SECT. 904.3.1. NONE IS SHOWN ON
 SANITARY RISER DIAGRAM.
  
 6) DEMO PERMITS REQUIRED.
  
 7) PAGE P2, WATER HEATER DETAIL, PAN
 DRAIN FOR WATER HEATER EMERGENCY PAN
 SHALL BE 1"
  
 8) SEPARATE PERMITS REQUIRED FOR GAS AND
 IRRIGATION. PLUMBING CONTRACTOR SHALL
 CUT INTO WATER SERVICE AND LEAVE A VALVE
 AND AN ADAPTOR FOR IRRIGATION IF NONE IS
 AVAILABLE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377